Lochinvar 150 - 800 service manual Checking temperature sensors, Temperature F Resistance Ω

Page 23

Service Manual

3Troubleshooting (continued)

Checking temperature sensors

The water heater temperature sensors (inlet water, outlet water, system water, and flue) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.

Table 3B - Inlet/Outlet System Sensor Resistance vs. Temperature

Temperature °F

Resistance Ω

Temperature °F

Resistance Ω

 

 

 

 

50

18,780

158

1,990

 

 

 

 

68

12,263

176

1,458

86

8,194

194

1,084

 

 

 

 

104

5,592

212

817

122

3,893

--

--

140

2,760

--

--

 

 

 

 

 

 

 

 

Table 3C - Flue Temperature Sensor Resistance vs. Temperature

 

 

 

 

 

Temperature °F

Resistance Ω

Temperature °F

Resistance Ω

 

 

 

 

68

14,773

176

1,707

 

 

 

 

86

9,804

194

1,266

 

 

 

 

104

6,652

212

952

 

 

 

 

122

4,607

230

726

 

 

 

 

140

3,252

248

560

 

 

 

 

158

2,337

--

--

 

 

 

 

23

Image 23
Contents Models 150 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials Troubleshooting What is in this manual?Service MaintenanceArmor water heater display ServiceControl inputs Control outputs Saving parameters General OperationHow the water heater operates Sequence of operationSequence of operation Use this procedure to access menus from the display panel Display panel menu accessButton Operation Display Comments Display panel parameter accessWHR Parameter tableNot used Data logging Viewable and changeable control parametersNot used Control modes WHR settingsFunctions Circulation pumps Service NotificationOwner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check water heater relief valve Flue vent system and air pipingCheck water system Check expansion tankPerform start-up and checks Check ignition ground wiringCheck all water heater wiring Check control settingsOiled bearing circulators Check flame signalCleaning heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationTemperature F Resistance Ω Checking temperature sensorsOpening NoisyNo Pump Relief ValveGV/Relay Flow SwitchFlame SequenceNo Flame Ign Running No FlameFan Speed Low Manual ResetHigh Limit Fan LowSensor Shorted Fan HighFan Speed High Sensor OpenProgr Rem Ctrl FltParameters Low 24 VAC Service BlkWatch Dog Error No Error StoredGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionModel Gas valve adjustment procedureModels 150 Models 600 4Gas Valve Adjustment Model