| Service Manual | |
|
|
|
| |
1 Service (continued) |
|
| ||
Sequence of operation |
|
| ||
Table 1A Sequence of operation |
|
| ||
|
|
| ||
OPERATION |
| DISPLAY | ||
|
| |||
1. Upon a call for heat, the control turns on the water heater pump. | WHR: Standby | |||
|
| OUT: 123.8F(129) | ||
2. The control connects 120 VAC to the blower. The blower does not |
|
| ||
run at this time. |
|
| ||
• If the unit is equipped with a flow switch, it must close before the |
|
| ||
control powers up the blower. |
|
| ||
• The manual reset high limit must be closed before the control | WHR: Standby | |||
powers up the blower. | ||||
OUT: 123.8F(129) | ||||
• If the unit is equipped with a solenoid valve and/or a vent | ||||
valve, they will be energized along with the blower. |
|
| ||
• If the unit is equipped with a gas pressure switch, it must close |
|
| ||
at this time. |
|
| ||
• If there is an auxiliary device connected to the unit, the unit |
|
| ||
will then provide 24 VAC to its enable relay. If the auxiliary |
|
| ||
device has a proving switch, it must close before the |
|
| ||
sequence continues. |
|
| ||
|
| |||
3. The control then starts a 10 second prepurge cycle. | WHR: PREPURGE | |||
|
| OUT: 123.9F(129) | ||
4. Once the prepurge cycle is complete, and the blocked drain | WHR: IGNITION | |||
switch is closed, the control starts the 5 second trial for ignition by | ||||
sending spark voltage to the spark electrode and opening the gas | OUT: 123.9F(129) | |||
valve. | ||||
|
|
| ||
5. If the control does not detect flame by the end of the trial for |
|
| ||
ignition, the control performs a 10 second postpurge, another |
|
| ||
prepurge and tries to light the burner again. | WHR: POSTPURGE, PREPURGE | |||
If the burner does not light after 4 trials on Models 150 - 399, the | ||||
control locks out for 1 hour and then tries another set of 4 trials. | OUT: 123.9F(129) | |||
If the burner does not light after 1 retry on Models 500 - 800 the |
|
| ||
control will lock out. |
|
| ||
|
|
| ||
6. If the control detects a flame before the trial for ignition ends, it | WHR: WHR 20% RATE | |||
begins to modulate the burner in order to maintain the set point. | ||||
|
| OUT: 124.8F(129) | ||
|
|
| ||
7. Once the call for heat is satisfied, the control will turn off the burner. | WHR: POSTPURGE | |||
The blower will remain on for the 10 second postpurge cycle. The | ||||
water heater pump will continue to run for its pump delay time, | OUT: 127.4F(129) | |||
then turn off. | ||||
|
| |||
8. Water heater pump off. | WHR: Standby | |||
|
| OUT: 124.7F(129) |
9