Lochinvar 150 - 800 Service Blk, Low 24 VAC, Watch Dog Error, Write EEProm, CRC Parameters

Page 31

Service Manual

3Troubleshooting (continued)

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

While the unit is in Service Mode, the outlet

• Establish a heating load to remove the heat from the

 

temperature has exceeded 185°F.

water heater loop.

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

• Verify that the water heater is piped properly into the

 

 

heating system. Refer to Section 6 - System Piping

 

 

of the Armor Water Heater Installation and Operation

 

 

Manual for the proper piping methods for the Armor

Service Blk

 

water heater.

 

 

• Check 120 VAC to the water heater pump motor on a

 

 

call for heat. If voltage is not present, check the wiring

 

 

back to the main control board. Replace the main

 

 

control board if necessary.

 

 

• If 120 VAC is present on a call for heat and the water

 

 

heater pump is not operating, replace the pump.

 

 

• Verify that the water heater pump is set to the proper

 

 

speed or that the water heater pump is the proper

 

 

size. Reference Section 6 - System Piping of the

 

 

Armor Water Heater Installation and Operation

 

 

Manual for water heater pump specifications.

 

 

 

 

120 VAC input to the main control board has

• Check 120 VAC supply to the transformer.

 

dropped below 80 VAC.

 

Low 24 VAC

 

• Check wiring connections at the low voltage terminal

 

strip.

 

 

• Check the wire size/length to remote devices.

 

 

• Replace the transformer.

Watch Dog Error

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

Write EEProm

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

CRC Parameters

internal fault.

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

No Error Stored

internal fault.

 

 

 

 

31

Image 31
Contents Models 150 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid Troubleshooting What is in this manual?Service MaintenanceArmor water heater display ServiceControl inputs Control outputs Saving parameters General OperationHow the water heater operates Sequence of operationSequence of operation Use this procedure to access menus from the display panel Display panel menu accessButton Operation Display Comments Display panel parameter accessWHR Parameter tableNot used Data logging Viewable and changeable control parametersFunctions WHR settingsNot used Control modes Circulation pumps Service NotificationService technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check water heater relief valve Flue vent system and air pipingCheck water system Check expansion tankPerform start-up and checks Check ignition ground wiringCheck all water heater wiring Check control settingsOiled bearing circulators Check flame signalCleaning heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationTemperature F Resistance Ω Checking temperature sensorsOpening NoisyNo Pump Relief ValveGV/Relay Flow SwitchFlame SequenceNo Flame Ign Running No FlameFan Speed Low Manual ResetHigh Limit Fan LowSensor Shorted Fan HighFan Speed High Sensor OpenParameters Rem Ctrl FltProgr Low 24 VAC Service BlkWatch Dog Error No Error StoredGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionModels 150 Gas valve adjustment procedureModel Models 600 4Gas Valve Adjustment Model