GP_ATV58_EN.fm Page 103 Mardi, 2. avril 2002 6:09 18

Fault Menu

This menu can be accessed when the switch is in position .

Modifications can only be made in stop mode with the speed controller locked.

Code

Description

Factory setting

 

 

 

Atr

Auto Restart

No

 

 

 

This function is used to restart the speed controller automatically if a fault has disappeared (Yes/No option). Automatic restarting is possible after the following faults :

-line overvoltage

-DC bus overvoltage

-external fault

-motor phase loss

-serial link fault

-communication fault

-loss of 4-20 mA reference

-motor overload (condition : motor thermal state less than 100 %)

speed controller overheating (condition : speed controller thermal state less than 70 %)

-motor overheating (condition : resistance of probes less than 1,500 Ohms)

 

 

When the function is activated, following appearance of one or more of these faults, the R1 relay

 

 

stays closed: the drive attempts to start every 30 s. A maximum of 6 attempts are made with the

 

 

drive unable to start (fault present). If all 6 fail, the drive remains locked definitively with the fault relay

 

 

open, until it is reset by being switched off.

 

 

 

 

 

This function requires the associated sequence to be maintained. Ensure that accidental

 

 

 

 

 

 

 

 

 

 

restarting will not pose any danger to either equipment or personnel.

 

 

 

 

 

 

 

 

 

rSt Reset Type

 

 

RSP

 

 

 

 

 

 

 

This function can be accessed if the fault reset is assigned to a logic input.

 

 

2 possible options : partial reset (RSP), general reset (RSG)

 

 

Faults affected by a partial reset (rSt = RSP)

 

 

 

-

line overvoltage

-

DC bus overvoltage

 

 

 

-

motor overheating

-

loss of 4-20mA

 

 

 

-

motor overload

-

overhauling

 

 

 

-

motor phase loss

-

speed controller overheating

 

 

 

-

serial link fault

-

external fault

 

 

 

-

communication fault

-

overspeed

 

 

Faults affected by a general reset (rSt = RSG) : all faults. The general reset actually inhibits all the

 

 

faults (forced operation).

 

 

 

 

 

To configure rSt = RSG :

 

 

 

1

Display RSG.

 

 

 

2

Press the "ENT" key.

 

 

 

3The speed controller displays "See manual".

4 Press then then "ENT".

OPL OutPhaseLoss

Yes

 

 

 

Used to enable the motor phase loss fault.

(Fault is disabled if an isolator is used between the speed controller and the motor). Yes / No options

IPL InPhseLoss

Yes

 

 

 

Used to enable the line phase loss fault.

(Fault is disabled if there is a direct power supply via a DC bus, or a single phase supply to an ATV58•U72M2, U90M2, D12M2

Yes / No options

This fault does not exist on the ATV58•U09M2, U18M2, U29M2 and U41M2.