103
ENGLISH
Fault Menu
This menu can be accessed when the switch is in position .
Modifications can only be made in stop mode with the speed controller locked.
Code Description Factory setting
AA
AAtt
ttrr
rr

Auto Restart

No
This function is used to restart the speed controller automatically if a fault has disappeared (Yes/No
option). Automatic restarting is possible after the following faults :
-line overvoltage
-DC bus overvoltage
-external fault
-motor phase loss
-serial link fault
-communication fault
-loss of 4-20 mA reference
-motor overload (condition : motor thermal state less than 100 %)
speed controller overheating (condition : speed controller thermal state less than 70 %)
-motor overheating (condition : resistance of probes less than 1,500 Ohms)
When the function is activated, following appearance of one or more of these faults, the R1 relay
stays closed: the drive attempts to start every 30 s. A maximum of 6 attempts are made with the
drive unable to start (fault present). If all 6 fail, the drive remains locked definitively with the fault relay
open, until it is reset by being switched off.
This function requires the associated sequence to be maintained. Ensure that accidental
restarting will not pose any danger to either equipment or personnel.
rr
rrSS
SStt
tt

Reset Type

RSP
This function can be accessed if the fault reset is assigned to a logic input.
2 possible options : partial reset (RSP), general reset (RSG)
Faults affected by a partial reset (rSt = RSP)
-line overvoltage
-motor overheating
-motor overload
-motor phase loss
-serial link fault
-communication fault
-DC bus overvoltage
-loss of 4-20mA
-overhauling
-speed controller overheating
-external fault
-overspeed
Faults affected by a general reset (rSt = RSG) : all faults. The general reset actually inhibits all the
faults (forced operation).
To configure rSt = RSG :
1Display RSG.
2Press the "ENT" key.
3The speed controller displays "See manual".
4Press
then
then "ENT".
OO
OOPP
PPLL
LL

OutPhaseLoss

Yes
Used to enable the motor phase loss fault.
(Fault is disabled if an isolator is used between the speed controller and the motor).
Yes / No options
II
IIPP
PPLL
LL

InPhseLoss

Yes
Used to enable the line phase loss fault.
(Fault is disabled if there is a direct power supply via a DC bus, or a single phase supply to an
ATV58•U72M2, U90M2, D12M2
Yes / No options
This fault does not exist on the ATV58•U09M2, U18M2, U29M2 and U41M2.
GP_ATV58_EN.fm Page 103 Mardi, 2. avril 2002 6:09 18