ENGLISH

GP_ATV58_EN.fm Page 78 Mardi, 2. avril 2002 6:09 18

Adjust Menu

The following parameters can be accessed once the I/O have been reassigned on the basic product.

Code

Description

 

 

Adjustment range

 

Factory setting

 

 

 

 

 

 

 

AC2

Accel. 2

-

s

0.05 to 999.9

 

5 s

 

 

 

 

 

 

2nd acceleration ramp

 

 

 

 

 

 

 

 

 

 

dE2

Decel. 2

-

s

0.05 to 999.9

 

5 s

 

 

 

 

 

 

2nd deceleration ramp

 

 

 

 

These parameters can be accessed if the ramp switching time (parameter Frt) is other than 0 Hz or

 

if a logic input is assigned to ramp switching.

 

 

 

 

 

 

 

IdC

DC Inj.curr -

A

0.10 to 1.36 In (1)

 

Acc. to controller rating

 

 

 

 

 

 

DC injection braking current

 

 

 

 

This parameter can be accessed if a logic input is assigned to DC injection stopping.

 

After 30 seconds the injection current is peak limited to 0.5 Ith if it is set at a higher value

 

 

 

 

 

SP2

Preset Sp.2 - Hz

LSP to HSP

 

10 Hz

 

 

 

 

 

 

 

2nd preset speed

 

 

 

 

 

 

 

 

 

SP3

Preset Sp.3 - Hz

LSP to HSP

 

15 Hz

 

 

 

 

 

 

 

3rd preset speed

 

 

 

 

 

 

 

 

 

SP4

Preset Sp.4 - Hz

LSP to HSP

 

20 Hz

 

 

 

 

 

 

 

4th preset speed

 

 

 

 

 

 

 

 

 

SP5

Preset Sp.5 - Hz

LSP to HSP

 

25 Hz

 

 

 

 

 

 

 

5th preset speed

 

 

 

 

 

 

 

 

 

SP6

Preset Sp.6 - Hz

LSP to HSP

 

30 Hz

 

 

 

 

 

 

 

6th preset speed

 

 

 

 

 

 

 

 

 

SP7

Preset Sp.7 - Hz

LSP to HSP

 

35 Hz

 

 

 

 

 

 

 

7th preset speed

 

 

 

 

 

 

 

 

 

 

JOG

Jog Freq.

- Hz

0 to 10 Hz

 

10 Hz

 

 

 

 

 

 

 

 

Jog frequency

 

 

 

 

 

 

 

 

 

 

 

 

JGt

JOG Delay

-

s

0 to 2 s

 

0.5 s

 

 

 

 

 

 

Anti-BrkLgSeqFlwd delay between two consecutive jog operations

 

 

 

 

 

 

brL

BrReleaseLev- Hz

0 to 10 Hz

 

0 Hz

 

 

 

 

 

 

Brake release frequency

 

 

 

 

 

 

 

 

 

Ibr

BrRelease I -

A

0 to 1.36In(1)

 

0 A

 

 

 

 

 

 

Brake release current

 

 

 

 

 

 

 

 

 

brt

BrReleasTime-

s

0 to 5 s

 

0 s

 

 

 

 

 

 

Brake release time

 

 

 

 

 

 

 

 

bEn

BrEngage Lev- Hz

0 to LSP

 

0 Hz

 

 

 

 

 

 

Brake engage frequency

 

 

 

 

 

 

 

 

bEt

BrEngageTime- Hz

0 to 5 s

 

0 s

 

 

 

 

 

 

Brake engage time

 

 

 

 

 

 

 

 

 

 

(1)In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller identification label for "high torque" applications.

78

Page 224
Image 224
Schneider Electric vw3-a58101 05 to 2nd acceleration ramp, 05 to 2nd deceleration ramp, LSP to HSP 10 Hz, LSP to HSP 15 Hz