Drive Menu

This menu can be accessed when the switch is in position .

The parameters can only be modified in stop mode with the speed controller locked.

Drive performance can be optimized by :

-entering the values given on the rating plate in the drive menu

-performing an auto-tune operation (on a standard asynchronous motor)

When using special motors (motors connected in parallel, tapered rotor brake motors, synchronous or synchronized asynchronous motors, rheostatic rotor asynchronous motors) :

-Select the “Hdg : Handling” or the “GEn : General Use” macro-configuration.

-Set the “SPC” Special motor parameter to “Yes” in the drive menu.

-Adjust the “UFr” IR compensation parameter in the adjust menu to obtain satisfactory operation.

Code

Description

Adjustment range

Factory setting

 

 

 

 

UnS

Nom.Mot.Volt - V

200 to 240V

230 V (2)

 

 

200 to 500 V

400/460V (2)

 

 

 

 

 

Nominal motor voltage given on the rating plate

 

 

The adjustment range depends on the speed controller model :

 

 

ATV58••••M2

 

 

 

ATV58••••N4

 

 

 

 

 

 

FrS

Nom.Mot.Freq- Hz

10 to 500 Hz

50/60Hz (2)

 

 

 

 

 

Nominal motor frequency given on the rating plate

 

 

 

 

 

nCr

Nom.Mot.Curr - A

0.25 to 1.36 In (1)

acc. to controller rating

 

 

 

 

 

Nominal motor current given on the rating plate

 

 

 

 

 

nSP

Nom.MotSpeed-rpm

0 to 9999 rpm

acc. to controller rating

 

 

 

 

 

Nominal motor speed given on the rating plate

 

 

 

 

 

COS

Mot. Cos Phi

0.5 to 1

acc. to controller rating

 

 

 

 

 

Motor Cos Phi given on the rating plate

 

 

 

 

 

tUn

Auto Tuning

No - Yes

No

 

 

 

 

 

Used to auto-tune motor control once this parameter has been set to “Yes”.

 

Once auto-tuning is complete, the parameter automatically returns to “Done”, or to “No” in the event

 

of a fault.

 

 

 

Caution : auto-tuning is only performed if no command has been activated. If a "freewheel stop" or

 

"fast stop" function is assigned to a logic input, this input must be set to 1 (active at 0).

 

 

 

 

tFr

Max. Freq. - Hz

10 to 500 Hz

60/72Hz (2)

 

 

 

 

 

Maximum output frequency.

 

 

 

The maximum value is a function of the switching frequency. See SFR parameter (drive menu).

 

 

 

 

nLd

Energy Eco

No-Yes

Yes

 

 

 

 

 

Optimizes motor efficiency.

 

 

 

Can only be accessed in the variable torque macro-configuration.

 

 

 

 

 

(1)In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller identification label for "high torque" applications.

(2)according to position of 50/60Hz switch.