GP_ATV58_EN.fm Page 109 Mardi, 2. avril 2002 6:09 18

Maintenance

Fault displayed

Probable cause

Procedure, remedy

 

 

 

EEF

• error saving in EEPROM

• cut the power supply to the speed

EEprom Fault

 

 

controller and reset

 

 

 

 

InF

internal fault

• check the connectors in the speed

Internal Fault

connector fault

controller

 

 

 

EPF

• fault triggered by an external device

• check the device which has caused the

External Fault

 

 

fault and reset

 

 

 

 

SPF

no speed feedback

• check the connection and the

Sp. Feedbk. Loss

 

 

mechanical coupling of the speed

 

 

 

sensor

 

 

 

 

AnF

non-following of ramp

• check the speed feedback setting and

Load Veer. Flt

 

speed inverse to the setpoint

wiring

 

 

 

• check the suitability of the settings for

 

 

 

the load

 

 

 

• check the size of the motor - speed

 

 

 

controller and the possible need for a

 

 

 

braking resistor

 

 

 

 

SOF

instability

• check the settings and the parameters

Overspeed

 

driving load too high

add a braking resistor

 

 

 

• check the size of the motor/speed

 

 

 

controller/load

 

 

 

CnF

• communication fault on the fieldbus

• check the network connection to the

Network Fault

 

 

speed controller

 

 

 

• check the time-out

 

 

 

ILF

• communication fault between the option

• check the connection of the option card

Int. Comm. Flt

 

card and the control card

to the control card

 

 

 

CFF

Error probably caused when changing

• check the hardware configuration of the

 

the card :

speed controller (power card, others)

Rating Fault-ENT

• change of rating of the power card

• cut the power supply to the speed

Option Fault-ENT

• change of the type of option card or

controller then reset

 

 

installation of an option card if there

• save the configuration in a file on the

 

 

was not one already and if the macro-

display module

 

 

configuration is CUS

• press ENT to return to the factory

Opt. Missing-ENT

option card removed

settings

CKS Fault - ENT

inconsistent configuration saved

 

 

The following message appears when

 

 

ENT is pressed :

 

 

Fact.Set? ENT/ESC

 

 

 

 

CFI

• inconsistent configuration sent to speed

• check the configuration sent previously

Config. Fault

 

controller via serial link

• send a consistent configuration

 

 

 

 

109

ENGLISH

Page 255
Image 255