Display Menu

Display menu (selection of parameter displayed during operation)

The following parameters can be accessed whatever position the access switch is in, in stop or run mode.

Code

Function

Unit

 

 

 

 

Var. State

 

 

 

---

State of the speed controller : indicates a fault or the motor operating phase :

 

rdY

rdY = speed controller ready,

 

rUn

rUn = motor in steady state or run command present and zero reference,

 

ACC

ACC = accelerating,

 

dEC

dEC = decelerating,

 

CLI

CLI = current limit,

 

dCb

dCb = injection braking,

 

nSt

nSt = freewheel stop control,

 

Obr

Obr = braking by adapting the deceleration ramp (see the “drive” menu).

 

 

 

 

FrH

Freq. Ref.

Hz

 

 

 

 

Frequency reference

 

 

 

 

rFr

Output Freq.

Hz

 

 

 

 

Output frequency applied to the motor

 

 

 

 

SPd

Motor Speed

rpm

 

 

 

 

Motor speed estimated by the speed controller

 

 

 

 

LCr

MotorCurrent

A

 

 

 

 

Motor current

 

 

 

 

USP

Mach. speed

 

 

 

 

Machine speed estimated by the speed controller. This is proportional to rFr, according to a

 

coefficient USC which can be regulated in the adjust menu. Displays a value corresponding to the

 

application (metres / second, for example). Caution, if USP becomes greater than 9999 the display

 

isdivided by 1000.

 

 

 

 

OPr

Output power

%

 

 

 

 

Power supplied by the motor, estimated by the controller.

 

 

100 % corresponds to nominal power.

 

 

 

 

ULn

MainsVoltage

V

 

 

 

 

Line voltage

 

 

 

 

tHr

MotorThermal

%

 

 

 

 

Thermal state : 100% corresponds to the nominal thermal state of the motor. Above 118%, the

 

speed controller triggers an OLF fault (motor overload)

 

 

 

 

tHd

DriveThermal

%

 

 

 

 

Thermal state of the speed controller : 100% corresponds to the nominal thermal state of the speed

 

controller. Above 118%, the speed controller triggers an OHF fault (speed controller overheating).

 

It can be reset below 70 %.

 

 

 

 

LFt

Last Fault

 

 

 

 

Displays the last fault which occurred.

 

 

 

 