77
ENGLISH
Adjust Menu
The following parameters can be accessed in the ‘general use’ macro-configuration
The following parameters can be accessed in the ‘variable torque’ macro-configuration
(1) 100% corresponds to the nominal torque of a motor with a power rating equal to that associated with the
speed controller in high torque applications.
(2) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
Code Description Adjustment range Factory setting
UU
UUFF
FFrr
rr
IR Compens. - %
0 to 150% or 0 to 800% 100%
Used to adjust the default value or the measured value during auto-tuning.
The adjustment range is extended to 800% if the SPC parameter (special motor) is set to “Yes” in
the drive menu.
SS
SSLL
LLPP
PP
Slip Comp. - %
0 to 150% 100%
Used to adjust the slip compensation value fixed by the motor nominal speed.
JJ
JJOO
OOGG
GG
Jog Freq. - Hz
0 to 10 Hz 10 Hz
Jog frequency
JJ
JJGG
GGtt
tt
JOG Delay - s
0 to 2 s 0.5 s
Anti-repeat delay between two consecutive jog operations
tt
ttLL
LL22
22
Trq.Limit 2 - %
0 to 200% (1) 200%
Second torque limit level activated by a logic input
Code Description Adjustment range Factory setting
II
IIdd
ddCC
CC
DC Inj.curr - A
0.10 to 1.36 In (2) Acc. to controller rating
DC injection braking current.
After 30 seconds the injection current is peak limited to 0.5 Ith if it is set at a higher value
PP
PPFF
FFLL
LL
U/f Profile - %
0 to 100% 20%
Used to adjust the quadratic power supply ratio when the energy saving function has been inhibited
Parameters in gray boxes appear if an I/O extension card is installed
GP_ATV58_EN.fm Page 77 Mardi, 2. avril 2002 6:09 18