GP_ATV58_EN.fm Page 74 Mardi, 2. avril 2002 6:09 18

Adjust Menu

ENGLISH

This menu can be accessed when the switch is in positions and . Adjustment parameters can be modified in stop mode OR during operation. Ensure that any changes made during

operation are not dangerous; changes should preferably be made in stop mode.

The list of adjustment parameters is made up of a fixed and a changeable part which varies according to :

-the selected macro-configuration

-the presence of an I/O extension card

-the reassignment of I/O

The following parameters can always be accessed in all the macro-configurations.

Code

Description

 

Adjustment range

Factory setting

 

 

 

 

 

LFr

Freq. Ref.

- Hz

LSP to HSP

 

 

 

 

 

Appears when control via the display module is activated : LCC parameter in the control menu

 

 

 

 

ACC

Acceleration - s

0.05 to 999.9

3 s

dEC

Deceleration - s

0.05 to 999.9

3 s

 

 

 

 

 

Acceleration and deceleration ramp times. Ranges 0 to motor nominal frequency (FrS)

 

 

 

 

AC2

Accelerate 2 - s

0.05 to 999.9

5 s

dE2

Decelerate 2 - s

0.05 to 999.9

5 s

 

 

 

 

 

2nd acceleration ramp

 

 

 

2nd deceleration ramp

 

 

 

These parameters can be accessed if the ramp switching threshold (parameter Frt) is other than 0

 

Hz or if a logic input is assigned to ramp switching.

 

 

 

 

 

 

LSP

Low Speed

- Hz

0 to HSP

0 Hz

 

 

 

 

 

 

Low speed

 

 

 

 

 

 

 

 

HSP

High Speed

- Hz

LSP to tFr

50 / 60 Hz

 

 

 

 

acc. to the switch

 

 

 

 

 

High speed : ensure that this setting is correct for the motor and the application.

 

 

 

 

 

FLG

Gain

- %

0 to 100

20

 

 

 

 

 

Frequency loop gain : used to adapt the rapidity of the machine speed transients according to the

 

dynamics.

 

 

 

 

For high resistive torque, high inertia or fast cycle machines, increase the gain gradually.

 

 

 

 

 

StA

Stability

- %

0 to 100

20

 

 

 

 

 

Used to adapt the return to steady state after a speed transient according to the dynamics of the

 

machine.Gradually increase the stability to avoid any overspeed.

 

 

 

 

 

ItH

ThermCurrent - A

0.25 to 1.36 In (1)

According to controller rating

 

 

 

 

 

Current used for motor thermal protection. Set ItH to the nominal current on the motor rating plate.

 

 

 

 

tdC

DC Inj. Time - s

0 to 30 s Cont

0.5 s

 

 

 

 

 

DC injection braking time.

 

 

 

If this is increased to more than 30 s, "Cont" is displayed, permanent DC injection.

 

The injection becomes equal to SdC after 30 seconds.

 

 

 

 

 

 

(1)In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller identification label for high torque applications.

74

Page 220
Image 220
Schneider Electric vw3-a58101, altivar 58 telemecanique manual Adjust Menu