Schneider Electric vw3-a58101 manual Malfunction with no fault display, Or not illuminated

Models: vw3-a58101 altivar 58 telemecanique

1 294
Download 294 pages 38.42 Kb
Page 256
Image 256

ENGLISH

GP_ATV58_EN.fm Page 110 Mardi, 2. avril 2002 6:09 18

Maintenance

Malfunction with no fault display

Display

Probable cause

Procedure, remedy

 

 

 

 

No code, LEDs not

No power supply

• Check power supply to speed controller

illuminated

 

 

 

 

 

 

 

No code, green

Display module defective

• Change the display module

LED illuminated,

 

 

 

red LED illuminated

 

 

 

or not illuminated

 

 

 

 

 

 

rdY

• Speed controller in line mode with

• Set parameter LI4 to forced local mode

green LED

 

communication card or RS485 kit

then use LI4 to confirm this forced

illuminated

• An LI input is assigned to “Freewheel

mode.

 

 

stop” or “Fast stop”, and this input is not

• Connect the input to 24 V to disable the

 

 

switched on.

stop.

 

 

These stops are controlled by loss of

 

 

 

the input.

 

 

 

 

 

110

Page 256
Image 256
Schneider Electric vw3-a58101 Malfunction with no fault display, Or not illuminated, Speed controller in line mode with