Maintenance

Fault displayed

Probable cause

Procedure, remedy

 

 

 

 

 

PHF

speed controller incorrectly supplied or

check the power connection and the fuses

Mains Phase Loss

 

fuses blown

reset

 

transient fault on one phase

configure the "In Phase Loss" (code

 

• use on a single phase supply of an

 

IPL) fault to "No", in the FAULT menu

 

 

ATV58•U72M2, U90M2 or a D12M2

 

 

 

 

(3-phase)

 

 

 

 

 

 

 

USF

line supply too low

check the line voltage

Undervoltage

transient voltage dip

 

 

 

damaged load resistor

change the load resistor

 

 

 

 

 

OSF

line supply too high

check the line voltage

Overvoltage

 

 

 

 

 

 

 

 

 

OHF

heatsink temperature too high

monitor the motor load, the speed

Drive Overheat

 

(tHd>118 %)

 

controller ventilation and wait for it to

 

 

 

 

cool down before resetting

 

 

 

 

 

OLF

thermal trip due to prolonged overload

check the thermal protection setting,

Mot Overload

 

(tHr>118 %)

 

monitor the motor load

 

 

 

a reset will be possible after approximately

 

 

 

 

7 minutes

 

 

 

 

 

ObF

braking too sudden or driving load

increase the deceleration time, add a

Overbraking

supply overvoltage during operation

 

braking resistor if necessary

 

 

 

check the possible supply overvoltage

 

 

 

 

 

OPF

one phase cut at the speed controller

Check the motor connections and the

Motor Phase Loss

 

output

 

operation of the output contactor (if fitted)

 

 

 

If a motor starter is used in macro

 

 

 

 

configuration, check the configuration of

 

 

 

 

the relay R2 and the output contactor

 

 

 

 

 

LFF

loss of the 4-20mA setpoint on input AI2

check the connection of the setpoint

Loss Follower

 

 

 

circuits

 

 

 

 

 

OCF

ramp too short

check the settings

Overcurrent

inertia or load too high

check the size of the motor/speed

 

mechanical locking

 

controller/load

 

 

 

check the state of the mechanism

 

 

 

 

 

SCF

short-circuit or grounding at the speed

check the connection cables with the

Short Circuit

 

controller output

 

speed controller disconnected, and the

 

 

 

 

motor insulation. Check the speed

 

 

 

 

controller transistor bridge

 

 

 

 

 

CrF

load relay control fault

check the connectors in the speed

Precharge Fault

damaged load resistor

 

controller and the load resistor

 

 

 

 

 

SLF

incorrect connection on the speed

check the connection on the speed

Serial Link Flt

 

controller terminal port

 

controller terminal port

 

 

 

 

 

OtF

motor temperature too high (PTC

check the motor ventilation and the ambi-

Motor Overheat

 

probes)

 

ent temperature, monitor the motor load

 

 

 

check the type of probes used

 

 

 

 

 

tSF

incorrect connection of probes to the

check the connection of the probes to

PTC Therm Sensor

 

speed controller

 

the speed controller

 

 

 

check the probes

 

 

 

 

 

 

 

 

 

 

108

 

 

 

 