Control Menu

Code Description

Adjustment range

Factory setting

AOL

 

AO Min. Val- mA

 

 

0 to 20 mA

0 mA

AOH

 

AO Max. Val- mA

 

 

0 to 20 mA

20 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. and max. value of the signal on output AO and AO1 (1).

 

 

Parameter

 

 

 

 

Max

 

 

 

 

 

 

 

These two parameters are used to define the output signal on AO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and AO1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eg. : 0-20 mA, 4-20 mA, 20-4mA, etc

 

 

0

 

 

 

 

 

 

AO (mA)

 

 

 

 

 

 

AOL AOH

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Str

 

Save Ref.

 

 

NO-RAM-EEP

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Associated with the +/- speed function, this function is used to save the reference :

when the run commands disappear (save in RAM) or when the line supply disappears (save in

EEPROM)

On the next start-up, the speed reference is the last reference saved.

LCC Keypad Comm.

No-Yes

No

 

 

 

 

Used to activate speed controller control via the display module. The STOP/RESET, RUN and FWD/REV keys are active. The speed reference is given by the parameter LFr. Only the freewheel stop, fast stop and DC injection stop commands remain active at the terminals. If the speed controller / display module connection is cut, the speed controller locks in an SLF fault.

PSt STOP Priorit

No-Yes

Yes

 

 

 

 

This function gives priority to the STOP key irrespective of the control channel (terminals or fieldbus).

To set the PSt parameter to "No" :

1 - Display "No".

2 - Press the "ENT" key.

3 - The speed controller displays "See manual"

4 - Press then then "ENT".

For applications with continuous processes, it is advisable to configure the key as inactive (set to "No").

Add DriveAddress

0 to 31

0

 

 

 

 

Address of the speed controller when it is controlled via the display module port (with the display module and programming terminal removed)

tbr BdRate RS485

9600-19200

19200

 

 

 

 

Transmission speed via the RS485 serial link (effective on the next power-up) 9600 bps

19200 bps

If tbr 19200, the terminal can no longer be used. To reactivate the terminal, reconfigure tbr as 19200 via the serial link or revert to factory settings (see page 63).

rPr Reset counters

No-APH-RTH

No

 

 

 

 

KWh or operating time reset to 0 No: No

APH: KWh reset to 0

RTH: Operating time reset to 0

APH and RTH are active immediately. The parameter then automatically returns to NO. Press “ENT” to confirm the reset to 0 command.

(1) Analog output AO appear if an I/O extension card is installed

87

ENGLISH