Fault Menu

Code

Description

 

Factory setting

 

 

 

 

tHt

ThermProType

 

ACL

 

 

 

 

Defines the type of indirect motor thermal protection provided by the speed controller. If the PTC

 

probes are connected to the speed controller, this function is not available. No thermal protection :

 

NO: No Prot.

 

 

Self-cooled motor (ACL) : the speed controller takes account of a derating depending on the rotation

 

frequency.

 

 

Force-cooled motor (FCL) : the speed controller does not take account of a derating depending on

 

the rotation frequency.

 

 

 

 

LFL

LossFollower

 

No

 

 

 

 

 

Used to enable the loss of 4-20 mA reference fault.

 

 

This fault can only be configured if the min/max AI2 ref. parameters (CrL and CrH) are greater than

 

3 mA, or if CrL>CrH,

 

 

- No : no fault.

 

 

- Yes : immediate fault.

 

 

- STT : stop according to the parameter STT, without a fault restart on the return of the signal.

 

- LSF : stop according to the parameter STT, drive shows a fault after stopping.

 

- LFF : Force the speed to the value set by LFF.

 

 

-

RLS : maintain the speed reached when the 4-20mA disappeared without a fault, restart on

 

 

the return of the signal.

 

 

 

 

LFF

Flt. Speed 4-20

 

0

 

 

 

 

Fallback speed in the event of the loss of the 4-20mA signal. Can be adjusted from 0 to HSP.

 

 

 

FLr

Catch On Fly

 

No

 

 

 

 

 

Used to enable a smooth restart after one of the following events :

 

 

- loss of line supply or simple power off

 

 

- fault reset or automatic restart.

 

 

- freewheel stop or injection stop with logic input

 

 

- uncontrolled loss downstream of the speed controller

 

 

Yes / No options.

 

 

If relay R2 is assigned to the brake sequence function, the FLr parameter remains locked on No.

 

 

 

StP

Cont. Stop

 

No

 

 

 

 

Controlled stop on a line phase loss. This function is only operational if parameter IPL is set to No.

 

If IPL is set to Yes, leave StP in position No. Possible choices :

 

 

No : locking on loss of line supply

 

 

MMS : Maintain DC Bus : voltage for the speed controller control is maintained by the kinetic energy

 

restored by the inertia, until the USF fault (undervoltage) occurs

 

 

FRP : Follow ramp : deceleration following the programmed dEC or dE2 ramp until a stop or until

 

the USF fault (undervoltage) occurs. This operation does not exist on ATV58•U09M2, U18M2,

 

U29M2 and U41M2.

 

 

 

 

Sdd

RampNotFoll

 

Yes

 

 

 

 

This function can be accessed if feedback via tachogenerator or pulse generator is programmed.

 

When enabled, it is used to lock the speed controller, if a speed error is detected (difference

 

between the stator frequency and the measured speed). Yes / No options.

 

 

 

EPL

External fault

 

Yes

 

 

 

 

 

Defines the type of stop on externel fault:

 

 

 

-

Yes: immediate fault

 

 

-

LSF Stop+flt: stop according to the Stt parameter, then fault at the end of stopping

 

 

 

 

 

 

 

 

 

 