Service Manual
3Troubleshooting
Table 3D Troubleshooting Chart - Noisy System
FAULT |
|
|
| CAUSE |
|
|
| CORRECTIVE ACTION |
|
| |||||
|
|
|
|
|
|
|
|
| |||||||
| - Supply gas problem. Natural gas pressures |
|
|
|
|
|
|
| |||||||
| should be | between | 4 | inches | w.c. | and | • Refer to Section 7 - Gas Connections | of the Armor | |||||||
| 14 | inches | w.c. | LP | gas | pressures should | Water Heater Installation and Operation Manual for | ||||||||
| be | between | 8 | inches | w.c. | and | detailed information concerning the gas supply. |
|
| ||||||
| 14 inches w.c. |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| • Refer to the Gas Valve Adjustment Procedure on | ||||||
|
|
|
|
|
|
|
|
| pages | ||||||
| - Gas/air mixture problem. |
|
|
| setting. | Verify that the vent/air intake lengths | do | not | |||||||
|
|
|
| exceed the maximum listed in the General Venting | |||||||||||
|
|
|
|
|
|
|
|
| |||||||
Noisy |
|
|
|
|
|
|
|
| section of the Armor Water Heater Installation and | ||||||
|
|
|
|
|
|
|
| Operation Manual. |
|
|
|
| |||
Operation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • Refer to page 19 in this manual for the burner removal | |||||||
|
|
|
|
|
|
|
|
| |||||||
| - Dirty/damaged burner. |
|
|
| and inspection procedure. | Clean or replace the burner | |||||||||
|
|
|
|
|
|
|
|
| as necessary. |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| • Refer to Section 6 - System Piping of the Armor Water | ||||||
| - Low water flow through the heat exchanger. | Heater Installation and Operation Manual for minimum | |||||||||||||
|
|
|
|
|
|
|
|
| flow rates. |
|
|
|
|
| |
|
|
|
|
|
|
|
| ||||||||
| - Air in the piping system. |
|
|
| • Properly purge all air from the piping system. |
|
| ||||||||
|
|
|
|
|
|
| |||||||||
| - Low system water pressure. |
|
| • Verify system pressure is a minimum of 12 PSI. |
|
| |||||||||
|
|
|
|
|
|
|
|
|
| ||||||
| - Blown fuse. |
|
|
|
|
| • Replace fuse F5 on the control board, see page 21 of | ||||||||
|
|
|
|
|
| this manual. |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
No Pump |
|
|
|
|
|
|
|
|
|
|
| ||||
- Faulty pump. |
|
|
|
|
| • Replace pump. |
|
|
|
| |||||
Operation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- Faulty pump relay. |
|
|
|
| • Replace pump relay. |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
| ||||||||
| - Internal fault on control board. |
|
| • Replace main control board. |
|
|
| ||||||||
|
|
| |||||||||||||
Relief Valve | - System pressure exceeds relief valve | • Lower the system pressure below the 150 PSI rating of | |||||||||||||
Opening | setting. |
|
|
|
|
|
| the supplied relief valve. |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| • Check the wiring connections to switch. Wires should | ||||||
|
|
|
|
|
|
|
|
| be connected to the common and normally closed | ||||||
|
|
|
|
|
|
|
|
| terminals. |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| • Air intake lengths exceed the maximum allowed | ||||||
APS |
|
|
|
|
|
|
|
| lengths. Refer to Section 3 - General Venting of the | ||||||
|
|
|
|
|
|
|
| Armor Water Heater Installation and Operation Manual | |||||||
Open |
|
|
|
|
|
|
|
| for proper lengths. |
|
|
|
| ||
(will require a |
|
|
|
|
|
|
|
| • Check | for | obstruction | or blockage | in | the | air |
manual reset once the |
|
|
|
|
|
|
|
| intake pipes or at terminations. |
|
|
| |||
condition has been | Air pressure switch contacts are open. |
| • Check reference hoses connected to the air pressure | ||||||||||||
corrected. Press the |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
| switch for blockage or obstruction. |
|
|
| ||||
RESET button on the |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| • Inspect the burner. Reference page 19 of this manual | |||||||
SMART SYSTEM |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
| for removal | and cleaning procedures. | Replace if | |||||
display to reset.) |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
| necessary. |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| • Inspect the heat exchanger. Reference page 20 of this | ||||||
|
|
|
|
|
|
|
|
| manual for removal and cleaning procedures. Replace | ||||||
|
|
|
|
|
|
|
|
| if necessary. |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| • Faulty air pressure switch. Replace switch. |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
24