Lochinvar 150 - 800 service manual Models 600, 4Gas Valve Adjustment Model

Page 34

Service Manual

3Troubleshooting (continued)

Model 500

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-4. Using a screwdriver, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 32 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3F on page 32 or replace the gas valve.

Figure 3-4Gas Valve Adjustment: Model 500

Models 600 - 800

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 32 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3F on page 32 or replace the gas valve.

Figure 3-5Gas Valve Adjustment: Models 600 - 800

THROTTLE

ADJUSTMENT

SCREW

(REMOVE BLUE CAP)

34

Image 34
Contents Models 150 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid Maintenance What is in this manual?Service TroubleshootingService Armor water heater displayControl inputs Control outputs Sequence of operation General OperationHow the water heater operates Saving parametersSequence of operation Display panel menu access Use this procedure to access menus from the display panelDisplay panel parameter access Button Operation Display CommentsParameter table WHRViewable and changeable control parameters Not used Data loggingFunctions WHR settingsNot used Control modes Service Notification Circulation pumpsService technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check expansion tank Flue vent system and air pipingCheck water system Check water heater relief valveCheck control settings Check ignition ground wiringCheck all water heater wiring Perform start-up and checksReview with owner Check flame signalCleaning heat exchanger Oiled bearing circulatorsCheck control module fuses TroubleshootingBefore troubleshooting Check the followingOperation No DisplayNo Burner Unit Does NotChecking temperature sensors Temperature F Resistance ΩRelief Valve NoisyNo Pump OpeningSequence Flow SwitchFlame GV/RelayNo Flame Ign No Flame RunningFan Low Manual ResetHigh Limit Fan Speed LowSensor Open Fan HighFan Speed High Sensor ShortedParameters Rem Ctrl FltProgr No Error Stored Service Blk Watch Dog Error Low 24 VACOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureModels 150 Gas valve adjustment procedureModel 4Gas Valve Adjustment Model Models 600