3Troubleshooting (continued)

Gas valve adjustment procedure

If adjustment of the gas valve is deemed necessary, use the following procedures: (Note: The procedures below are model specific.)

Models 150 - 285

Locate the throttle adjustment screw on the side of the venturi valve (FIG. 3-2). Using a screwdriver, turn the screw a 1/4 turn clockwise to decrease CO2 levels or a 1/4 turn counterclockwise to increase CO2 levels. After performing one adjustment on the valve, follow the Combustion Analysis Procedure on page 32 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3F on page 32 or replace the gas valve.

Figure 3-2Gas Valve Adjustment: Models 150 - 285

Model 399

Locate the throttle adjustment screw on the top of the gas valve, see FIG. 3-3. Using a screwdriver, turn the screw 1/8 turn counterclockwise to increase CO2 levels or 1/8 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 32 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3F on page 32 or replace the gas valve.

Figure 3-3Gas Valve Adjustment: Model 399

THROTTLE ADJUSTMENT

SCREW

33

Image 33
Contents Models 150 Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid Service What is in this manual?Maintenance TroubleshootingArmor water heater display ServiceControl inputs Control outputs How the water heater operates General OperationSequence of operation Saving parametersSequence of operation Use this procedure to access menus from the display panel Display panel menu accessButton Operation Display Comments Display panel parameter accessWHR Parameter tableNot used Data logging Viewable and changeable control parametersWHR settings FunctionsNot used Control modes Circulation pumps Service NotificationMaintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Check water system Flue vent system and air pipingCheck expansion tank Check water heater relief valveCheck all water heater wiring Check ignition ground wiringCheck control settings Perform start-up and checksCleaning heat exchanger Check flame signalReview with owner Oiled bearing circulatorsBefore troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner No DisplayOperation Unit Does NotTemperature F Resistance Ω Checking temperature sensorsNo Pump NoisyRelief Valve OpeningFlame Flow SwitchSequence GV/RelayNo Flame Ign Running No FlameHigh Limit Manual ResetFan Low Fan Speed LowFan Speed High Fan HighSensor Open Sensor ShortedRem Ctrl Flt ParametersProgr Watch Dog Error Service BlkNo Error Stored Low 24 VACGas Valve Adjustment Combustion Analysis ProcedureOr Obstruction Gas Supply PressureGas valve adjustment procedure Models 150Model Models 600 4Gas Valve Adjustment Model