3Troubleshooting (continued)
Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT |
| DESCRIPTION |
| CORRECTIVE ACTION |
| |||
|
|
| ||||||
| The unit was running and lost the flame | • Inspect spark electrode and associated wiring for | ||||||
| signal. | This condition occurred four (4) | damage and connection. | Reference page 19 of this | ||||
| straight times. | manual for removal and cleaning procedures. Replace | ||||||
|
|
| if necessary. |
|
|
|
| |
| Exception: Models 500 - 800 will lock out | • Check for proper electrical grounding of unit. |
| |||||
| after one retry for ignition. It will require a |
| ||||||
| manual reset before attempting to fire again. | • Check | incoming | supply | gas pressure. Natural gas | |||
|
|
| pressures should be between 4 - | 14 inches | w.c. and | |||
|
|
| LP gas pressures should be between 8 - 14 inches w.c. | |||||
|
|
| Refer to Section 7 - Gas Connections of the Armor | |||||
|
|
| Water Heater Installation and Operation Manual for | |||||
|
|
| detailed information concerning the gas supply. | |||||
|
|
| • Verify that the plastic hose from the gas valve to the air | |||||
|
|
| inlet is connected and is not damaged. |
| ||||
|
|
| • Verify that the vent/air intake pipes are installed | |||||
|
|
| correctly and there are no obstructions. |
| ||||
No Flame |
|
| • Check for 24 VAC to the gas valve at the | |||||
|
| connection on the side of the main control board during | ||||||
Running |
|
| the ignition attempt. If no voltage is present, replace the | |||||
(will require a manual |
|
| main control board. |
|
|
| ||
|
|
|
|
|
|
|
| |
reset once the condition |
|
| • If 24 VAC is present at the main control board, check | |||||
has been corrected. |
|
| ||||||
|
| the wiring between the main control board and the gas | ||||||
Press the RESET button |
|
| ||||||
|
| valve. | Replace | the wiring if | necessary. | Do not | ||
on the SMART |
|
| ||||||
|
| disconnect the wiring from the gas valve and attempt to | ||||||
SYSTEM display to |
|
| ||||||
|
| measure voltage at that point. The main control board | ||||||
reset.) |
|
| ||||||
|
| can detect if the gas valve is not connected and will | ||||||
|
|
| ||||||
|
|
| display the GV / Relay Fail fault. |
|
| |||
|
|
| • If 24 VAC is present, check the outlet of the valve to | |||||
|
|
| ensure the valve is flowing gas. With a manometer | |||||
|
|
| connected to the outlet tap of the gas valve, when the | |||||
|
|
| unit is in the prepurge period, there should be a | |||||
|
|
| negative pressure present. When the valve is | |||||
|
|
| energized a change in pressure should occur. If the | |||||
|
|
| pressure change does not occur, the gas valve is not | |||||
|
|
| opening. Replace the gas valve. |
|
| |||
|
|
| • Inspect | flame | sensor | and | associated | wiring. |
|
|
| Reference page 19 of this manual for removal and | |||||
|
|
| cleaning procedures. Replace if necessary. |
| ||||
|
|
| • Inspect the burner. Reference page 19 of this manual | |||||
|
|
| for removal and cleaning procedures. Replace if | |||||
|
|
| necessary. |
|
|
|
| |
|
|
| • Replace the main control board. |
|
| |||
|
|
|
|
|
|
|
|
|