Lennox International Inc Merit Series 14ACX Units Installing Indoor Metering Device

Page 15

Installing Indoor Metering Device

This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or expansion valve metering device (purchased separately) at the indoor coil.

See the Lennox 14ACX Engineering Handbook for approved expansion valve kit match ups. The expansion valve unit can be installed internal or external to the indoor

coil. In applications where an uncased coil is being installed in a field−provided plenum, install the expansion valve in a manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit. .

After installation of the indoor coil metering device, proceed to Leak Test Line Set and Indoor Coil on page 16.

INDOOR EXPANSION VALVE INSTALLATION

TWO PIECE

(Uncased Coil Shown)

 

PATCH PLATE

 

(UNCASED

 

STUB

 

 

COIL ONLY)

LIQUID LINE

EXPANSION

 

END

 

 

ORIFICE

 

 

VALVE

 

 

 

 

 

HOUSING

 

 

DISTRIBUTOR

 

 

 

 

 

 

 

TUBES

 

 

 

TEFLON®

 

 

 

 

 

 

 

 

RING

 

 

TEFLON®

SENSING

 

 

RING

 

 

 

 

LINE

 

 

 

 

ARemove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s distributor assembly.

BInstall one of the provided Teflon® rings around the

stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon® ring with refrigerant oil.

CAttach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft−lb.

DPlace the remaining Teflon® washer around the other end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon® ring with refrigerant oil.

1/2 Turn

11 12

1

10

 

2

9

 

43

8 7

6

5

DISTRIBUTOREQUALIZER

ASSEMBLY LINE

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

EAttach the liquid line assembly to the expansion valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb.

SENSING BULB INSTALLATION

MALE EQUALIZER LINE

VAPOR

FITTING (SEE

LINE

EQUALIZER LINE

 

INSTALLATION FOR

 

FURTHER DETAILS)

 

Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.

AAttach the vapor line sensing bulb in the proper orientation as illustrated to the right using the clamp and screws provided.

NOTE

and expansion bulb before insulating the sensing bulb once LIQUID LINE installed.

BConnect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.

 

1/8 Turn

 

11 12

1

10

 

2

9

 

 

43

8

7

6

5

EQUALIZER LINE INSTALLATION

ARemove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.

BRemove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.

VAPOR LINE

ON LINES SMALLER THAN

7/8", MOUNT SENSING

 

BULB AT EITHER THE 3 OR

 

9 O’CLOCK POSITION.

 

12

BULB

BULB

FLARE SEAL CAP

OR

FLARE NUT

VAPOR LINE

 

 

 

 

 

ON 7/8" AND LARGER LINES,

 

 

MOUNT SENSING BULB AT

COPPER FLARE

 

EITHER THE 4 OR 8 O’CLOCK

SEAL BONNET

12

POSITION. NEVER MOUNT ON

 

BOTTOM OF LINE.

MALE BRASS EQUALIZER

BULB

BULB

LINE FITTING

 

 

 

VAPOR LINE

NOTE OM OF LINE.

Figure 12. Installing Indoor Expansion Valve

Page 15

14ACX SERIES

Image 15
Contents Condensing Units Table of ContentsShipping and Packing List GeneralSide View Unit Dimensions − Inches mmModel Number Identification AC X −024 − 230 −13 Typical Unit Parts ArrangementTorque Requirements Operating Manifold Gauge Set and Service ValvesUsing Manifold Gauge SET Operating Service Valves11 12 98 7 6 2CONNECT Manifold Gauge SET Recovering Refrigerant from Existing System1DISCONNECT Power Recovering RefrigerantPositioning Considerations New Unit PlacementClearance on ALL Sides Minimum Clearance Above Unit Minimum Clearance Between TWO UnitsStep Removing and Installing LouversPlacing Unit on Slab Roof MountingMineral oils are not compatible with HFC−410A. If oil New or Replacement Line SetRefrigerant Line SET From Vertical to Horizontal InstallationRefrigerant Line SET Alling Vertical Runs NEW Construction ShownBrazing Connections 1CUT and Debur Brazing Procedures7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SETFlushing Line Set and Indoor Coil 2CONNECT Gauges and Equipment for Flushing ProcedureEqualizer Line Installation Installing Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationLeak detector must be capable of sensing HFC refrigerant Leak Test Line Set and Indoor CoilConnect Gauge SET Evacuating Line Set and Indoor Coil24VAC Transformer ElectricalLOW Voltage Control Wiring Single Phase High Voltage / Ground WiresTypical Factory Wiring Diagram Copeland Compressor Typical Factory Wiring Diagram Interlink Compressor System Refrigerant Connections for Testing and ChargingServicing Units Delivered Void of Charge Unit Start−UpStart Determine how refrigerant is metered Checking AIR Flow AT Indoor CoilBelow Calculating System Charge for Outdoor Unit Void of ChargeHFC−410A Subcooling TXV Charge Superheat RFC Start Measure outdoor ambient temperatureProblem exists with some component in the system Maintenance System OperationUnit Components Homeowner Start−Up and Performance Checklist