Lennox International Inc Merit Series 14ACX Units, CONDENSING UNITS installation instructions

Page 27

Table 4. HFC−410A Normal Operating Pressures (Liquid +10 and Suction +5 psig)

 

 

 

 

Use this table to perform maintenance checks; it is not a procedure for charging the

IMPORTANT

system. Minor variations in these pressures may be due to differences in installations.

Significant deviations could mean that the system is not properly charged or that a

 

 

 

 

problem exists with some component in the system.

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

−018

−024

 

−030

−036

−041

−042

−047

−048

−059/−060

 

 

 

 

 

 

 

 

 

 

 

**Temp.

Liquid /

Liquid /

 

Liquid /

Liquid /

Liquid /

Liquid /

Liquid /

Liquid /

Liquid /

5F (5C)

Suction

Suction

 

Suction

Suction

Suction

Suction

Suction

Suction

Suction

 

 

 

 

 

 

 

 

 

 

 

Expansion Valve (TXV)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65 (18)

230 / 138

225 / 135

 

226 / 129

238 / 132

233 / 142

236 / 138

233 / 139

238 / 136

239 / 133

 

 

 

 

 

 

 

 

 

 

 

70 (21)

244 / 139

242 / 137

 

241 / 131

254 / 135

239 / 142

253 / 140

252 / 140

256 / 138

258 / 135

 

 

 

 

 

 

 

 

 

 

 

75 (24)

265 / 140

260 / 138

 

259 / 134

273 / 138

256 / 143

273 / 141

272 / 141

277 / 139

278 / 136

 

 

 

 

 

 

 

 

 

 

 

80 (27)

286 / 140

282 / 140

 

281 / 138

293 / 140

278 / 144

296 / 142

294 / 142

299 / 140

300 / 137

 

 

 

 

 

 

 

 

 

 

 

85 (29)

307 / 142

304 / 141

 

301 / 140

316 / 142

299 / 145

318 / 143

315 / 142

320 / 139

323 / 138

 

 

 

 

 

 

 

 

 

 

 

90 (32)

330 / 143

326 / 142

 

324 / 141

340 / 143

321 / 145

341 / 144

338 / 144

343 / 140

346 / 139

 

 

 

 

 

 

 

 

 

 

 

95 (35)

351 / 144

351 / 142

 

348 / 142

366 / 144

343 / 146

366 / 146

361 / 144

369 / 141

370 / 140

 

 

 

 

 

 

 

 

 

 

 

100 (38)

380 / 144

376 / 144

 

372 / 143

392 / 145

366 / 147

392 / 147

387 / 144

395 / 142

396 / 142

 

 

 

 

 

 

 

 

 

 

 

105 (41)

407 / 145

403 / 145

 

399 / 144

420 / 147

389 / 148

417 / 148

413 / 145

422 / 144

415 / 143

 

 

 

 

 

 

 

 

 

 

 

110 (43)

436 / 146

433 / 145

 

428 / 145

449 / 148

421 / 149

445 / 149

442 / 148

450 / 146

449 / 145

 

 

 

 

 

 

 

 

 

 

 

115 (45)

466 / 147

463 / 147

 

456 / 146

480 / 149

452 / 151

475 / 151

465 / 148

481 / 148

476 / 147

 

 

 

 

 

 

 

 

 

 

 

Fixed Orifice (RFC)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65 (18)

232 / 124

228 / 125

 

229 / 128

241 / 131

228 / 131

248 / 135

232 / 125

240 / 126

244 / 125

 

 

 

 

 

 

 

 

 

 

 

70 (21)

248 / 127

244 / 127

 

243 / 129

258 / 134

245 / 135

266 / 138

249 / 129

260 / 129

263 / 128

 

 

 

 

 

 

 

 

 

 

 

75 (24)

267 / 131

261 / 131

 

261 / 132

277 / 136

263 / 138

285 / 141

268 / 133

281 / 133

281 / 131

 

 

 

 

 

 

 

 

 

 

 

80 (27)

286 / 135

284 / 134

 

284 / 135

298 / 139

284 / 141

305 / 143

286 / 136

301 / 135

303 / 134

 

 

 

 

 

 

 

 

 

 

 

85 (29)

307 / 138

303 / 137

 

305 / 138

321 / 141

306 / 144

327 / 145

312 / 140

324 / 138

324 / 136

 

 

 

 

 

 

 

 

 

 

 

90 (32)

328 / 141

325 / 140

 

327 / 140

342 / 143

327 / 146

349 / 147

332 / 142

346 / 140

347 / 139

 

 

 

 

 

 

 

 

 

 

 

95 (35)

351 / 143

347 / 142

 

349 / 142

366 / 145

348 / 148

372 / 149

357 / 144

371 / 142

370 / 141

 

 

 

 

 

 

 

 

 

 

 

100 (38)

375 / 146

370 / 144

 

372 / 144

392 / 147

372 / 149

396 / 150

379 / 146

395 / 144

394 / 143

 

 

 

 

 

 

 

 

 

 

 

105 (41)

400 / 148

394 / 146

 

396 / 146

416 / 149

395 / 151

421 / 152

406 / 149

420 / 146

418 / 145

 

 

 

 

 

 

 

 

 

 

 

110 (43)

426 / 150

420 / 148

 

422 / 148

446 / 151

424 /153

447 / 153

430 / 150

447 / 148

444 / 146

 

 

 

 

 

 

 

 

 

 

 

115 (46)

457 / 153

447 / 150

 

449 / 150

480 / 152

453 / 155

476 / 154

460 / 152

473 / 150

471 / 147

 

 

 

 

 

 

 

 

 

 

 

*Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary. **Temperature of the air entering the outside coil.

Page 27

14ACX SERIES

Image 27
Contents Condensing Units Table of ContentsShipping and Packing List GeneralSide View Unit Dimensions − Inches mmModel Number Identification AC X −024 − 230 −13 Typical Unit Parts ArrangementTorque Requirements Operating Manifold Gauge Set and Service ValvesUsing Manifold Gauge SET Operating Service Valves11 12 98 7 6 2CONNECT Manifold Gauge SET Recovering Refrigerant from Existing System1DISCONNECT Power Recovering RefrigerantPositioning Considerations New Unit PlacementClearance on ALL Sides Minimum Clearance Above Unit Minimum Clearance Between TWO UnitsStep Removing and Installing LouversPlacing Unit on Slab Roof MountingMineral oils are not compatible with HFC−410A. If oil New or Replacement Line SetRefrigerant Line SET From Vertical to Horizontal InstallationRefrigerant Line SET Alling Vertical Runs NEW Construction ShownBrazing Connections 1CUT and Debur Brazing Procedures7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SETFlushing Line Set and Indoor Coil 2CONNECT Gauges and Equipment for Flushing ProcedureEqualizer Line Installation Installing Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationLeak detector must be capable of sensing HFC refrigerant Leak Test Line Set and Indoor CoilConnect Gauge SET Evacuating Line Set and Indoor Coil24VAC Transformer ElectricalLOW Voltage Control Wiring Single Phase High Voltage / Ground WiresTypical Factory Wiring Diagram Copeland Compressor Typical Factory Wiring Diagram Interlink Compressor System Refrigerant Connections for Testing and ChargingServicing Units Delivered Void of Charge Unit Start−UpStart Determine how refrigerant is metered Checking AIR Flow AT Indoor CoilBelow Calculating System Charge for Outdoor Unit Void of ChargeHFC−410A Subcooling TXV Charge Superheat RFC Start Measure outdoor ambient temperatureProblem exists with some component in the system Maintenance System OperationUnit Components Homeowner Start−Up and Performance Checklist