Lennox International Inc Comprehensive Guide to Lennox Merit Series Air Conditioners

Page 25

 

USE WEIGH-IN METHOD

 

65ºF (18.3ºC)

1.

Confirm proper airflow across coil using figure 19.

 

 

and above

2. Compare

unit pressures with table

4, Normal

 

 

 

 

 

 

 

 

 

 

Weigh-in or remove refrigerant

 

 

 

 

 

 

Operating Pressures.

 

 

 

based upon line length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Set thermostat to call for heat (must have a cooling load

 

 

 

 

 

 

 

 

 

 

 

ABOVE or

 

 

 

between 70-80ºF (21−26ºC)

 

 

 

 

 

 

 

 

64ºF (17.7ºC)

 

 

4.

Connect gauge set

 

 

 

 

 

 

 

 

 

BELOW

 

 

 

 

 

 

 

 

 

 

 

and below

 

 

 

5.

Measure outdoor ambient temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOCK OUTDOOR COIL: [sometimes necessary with lower

 

6.

When heat demand is satisfied, set thermostat to call for

 

 

 

 

 

 

 

 

cooling

 

 

 

 

 

 

 

 

 

temperatures] Use cardboard or plastic sheet to restrict the

 

 

 

 

 

 

 

 

 

 

 

 

7.

Allow temperatures and pressures to stabilize.

 

 

 

 

 

 

airflow through the outdoor coil to achieve pressures from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325−375 psig (2240−2585 kPa). Higher pressures are needed

 

 

NOTE − If necessary, block outdoor coil to maintain 325

 

 

 

 

 

 

to check charge. Block equal sections of air intake panels and

 

 

− 375 psig.

 

 

 

 

 

CARDBOARD OR

move coverings sideways until the liquid pressure is in the

 

8.

Record liquid line temperature:

 

 

 

above noted ranges.

 

 

 

 

 

 

 

 

 

 

 

 

LIQº = ______

 

 

 

 

 

PLASTIC SHEET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.

Measure liquid line pressure and use the value to

 

 

If refrigerant is added or

 

 

If value is MORE than shown,

 

 

 

 

 

 

 

 

 

 

 

determine saturation temperature (see table 3):

 

 

removed, verify charge using

 

 

remove refrigerant.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the Approach Method.

 

 

 

 

 

 

 

 

 

 

SATº = ______

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.

Subtract to determine subcooling (SCº):

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SATº_____ − LIQº _____ = SCº _____

 

 

 

 

 

If value is LESS

 

MORE or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11.

Compare results with table below.

 

 

 

 

 

than shown, add

 

 

 

 

 

 

 

 

 

 

 

 

LESS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ºF (ºC)*

 

 

−018

−024

 

−030

−036

−041

−042

−047

−048

−059/−060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65 (18)

 

10 (5.6)

10 (5.6)

 

11 (6.1)

13 (7.2)

 

9 (5.0)

 

10 (5.6)

6 (3.3)

8 (4.4)

8 (4.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 (24)

 

6 (3.3)

7 (3.9)

 

 

8 (4.4)

9 (5.0)

 

7 (3.9)

 

7 (3.9)

6 (3.3)

8 (4.4)

7 (3.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 (29)

 

6 (3.3)

8 (4.4)

 

 

6 (3.3)

7 (3.9)

 

7 (3.9)

 

8 (4.4)

6 (3.3)

8 (4.4)

8 (4.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95 (35)

 

6 (3.3)

9 (5.0)

 

 

6 (3.3)

8 (4.4)

 

7 (3.9)

 

8 (4.4)

6 (3.3)

8 (4.4)

7 (3.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105 (41)

 

 

10 (5.6)

9 (5.0)

 

 

7 (3.9)

9 (5.0)

 

7 (3.9)

 

8 (4.4)

6 (3.3)

8 (4.4)

6 (3.3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115 (45)

 

 

10 (5.6)

10 (5.6)

 

8 (4.4)

10 (5.6)

 

6 (3.3)

 

7 (3.9)

5 (2.8)

7 (3.9)

6 (3.3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Temperature of air entering outdoor coil.

Figure 23. HFC−410A Subcooling TXV Charge

Page 25

14ACX SERIES

Image 25
Contents Shipping and Packing List Table of ContentsGeneral Condensing UnitsSide View Unit Dimensions − Inches mmModel Number Identification AC X −024 − 230 −13 Typical Unit Parts ArrangementUsing Manifold Gauge SET Operating Manifold Gauge Set and Service ValvesOperating Service Valves Torque Requirements11 12 98 7 6 1DISCONNECT Power Recovering Refrigerant from Existing SystemRecovering Refrigerant 2CONNECT Manifold Gauge SETClearance on ALL Sides Minimum Clearance Above Unit New Unit PlacementMinimum Clearance Between TWO Units Positioning ConsiderationsPlacing Unit on Slab Removing and Installing LouversRoof Mounting StepMineral oils are not compatible with HFC−410A. If oil New or Replacement Line SetRefrigerant Line SET Alling InstallationVertical Runs NEW Construction Shown Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing ProceduresFlow Nitrogen Wrap Service Valves6BRAZE Line SET 7PREPARATION for Next StepFlushing Line Set and Indoor Coil 2CONNECT Gauges and Equipment for Flushing ProcedureIndoor Expansion Valve Installation Installing Indoor Metering DeviceSensing Bulb Installation Equalizer Line InstallationLeak detector must be capable of sensing HFC refrigerant Leak Test Line Set and Indoor CoilConnect Gauge SET Evacuating Line Set and Indoor Coil24VAC Transformer ElectricalLOW Voltage Control Wiring Single Phase High Voltage / Ground WiresTypical Factory Wiring Diagram Copeland Compressor Typical Factory Wiring Diagram Interlink Compressor Servicing Units Delivered Void of Charge Connections for Testing and ChargingUnit Start−Up System RefrigerantStart Determine how refrigerant is metered Checking AIR Flow AT Indoor CoilBelow Calculating System Charge for Outdoor Unit Void of ChargeHFC−410A Subcooling TXV Charge Superheat RFC Start Measure outdoor ambient temperatureProblem exists with some component in the system System Operation MaintenanceUnit Components Homeowner Start−Up and Performance Checklist