Raypak 2600401 Electrical Electronic Ignition IID, Intermittent Pilot System- Honeywell S8600

Page 32

TROUBLESHOOTING

Electrical

(Electronic Ignition IID)

Intermittent Pilot System— Honeywell S8600

WARNING: HIGH VOLTAGE: For qualified technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if the pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)

YES

SPARK ACROSS

IGNITER/SENSOR GAP

YES

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

 

 

 

NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout

 

 

 

procedure.

 

 

 

 

 

 

 

 

 

Check line voltage power, low voltage transformer, limit controller, thermostat

NO

 

 

(controller) and wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pull ignition lead and check spark at module.

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

Spark Okay?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

 

 

 

Check boot of the ignition cable for signs of melting or buckling. Take protective

 

 

 

 

action to shield cable and boot from excessive temperatures.

 

 

 

 

 

 

NO

 

Check that all manual gas valves are open, supply tubing and pressures are

 

 

 

 

good,

and pilot burner orifice is not blocked.

 

 

 

 

 

 

Check electrical connections between module and pilot operator on gas control.

 

 

 

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay,

 

 

 

 

replace gas control; if not, replace module.

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: If S8600H goes into lockout, reset system. Lockout is used on L.P.G.

 

 

 

models.

 

NO

 

• Check continuity of ignition cable and ground wire.

 

 

 

 

Clean flame rod.

 

 

 

Check electrical connections between flame rod and module.

 

 

 

Check for cracked ceramic flame rod insulator.

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

 

Adjust pilot flame.

 

 

 

If problem persists, replace module.

 

 

 

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

 

 

 

 

 

 

 

 

NOTE: IF S8600H goes into lockout, reset system.

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

Check continuity of ignition cable and ground wire.

 

 

 

 

 

 

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though

 

 

 

 

 

operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

 

Check for proper thermostat (controller) operation.

 

 

 

Remove MV lead at module; if valve closes, recheck temperature controller and

 

 

 

wiring; if not, replace gas valve.

Repeat procedure until troublefree operation is obtained.

32

Image 32
Contents Econopak Water Heaters Page Contents Are important but not related to personal injury hazards Temperature Time to Produce Serious Burn General SafetyTime/Temperature Relationships in Scalds General Specifications Receiving EquipmentTank Installation Code RequirementsMounting Base ClearancesVenting Connections Outdoor ModelsModels Model No Sq. in. of Each Free AreaIndoor Models Models 0260Vent Max Model No Connector Horizontal Diameter Length ft Vent Terminal/Indoor Stack InstallationCommon Vents Vent Pipe Draft Hood HeaterGas Supply Connections Model No Nat ProGas Pressure Specifications Type Inches WC Regulator Min SettingWater Connections & System Piping Gas Pressure RegulatorRelief Valve 0261 Low NOx WH1 with Pressure Relief ValveElectrical Wiring Wiring Diagrams Standing Pilot ModelIntermittent Ignition Device IID Model Intermittent Ignition Device IID Models 0330 Intermittent Ignition Device IID Model 0261 Low NOx Intermittent Ignition Device IID Models 0331 & 0401 Low NOx Sequence of Operation Servicing ProceduresStart-up Procedures Honeywellpilot Robertshaw Pilot For Robertshaw Gas Valve Turn gas control System Shut Down ProcedureFor Automatic Ignition Models Testing the Ignition Safety Shut-off To Turn Off Gas To ApplianceInspection Procedures ControlsLow NOx Heaters-Models BurnersBurner Adjustment High/Low Gas Pressure SwitchOperation Visual InspectionRepair Section Combustion Chamber Removal Heat Exchanger Re-assemblyHeat Exchanger Removal Troubleshooting CausesPiping Electrical Electronic Ignition IID Intermittent Pilot System- Honeywell S8600Electrical Standing Pilot Adjustments & Replacement of Components Circulator Replacement Control Well ReplacementTube Replacement Procedure Procedure for Cleaning Flue Gas Passage WaysLimitedpartswarrantyeconopakwaterheaters Page Page