Operation

On call for heat, the ignition system, consisting of an electronic spark module, gas pilot system is energized. Providing pilot is proven blower will start running, the main gas valve will open and the heater will operate. When the operating control is satisfied the heater will shut down.

Start-up Procedures (S8610B)

1.Turn on power to the heater with gas supply off.

2.Check ignition module as follows:

a.Set the thermostat or controller to call for heat.

b.Watch for continuous spark at the pilot burner.

c.Check the ignition spark operation. Time must be within the lockout timing period (15 or 90 seconds).

d.Turn control down to end call for heat and wait 60 seconds on lockout models before begin- ning step 3.

3.Turn on gas supply.

4.Set controller to call for heat.

5.System should start as follows:

a.Spark will turn on and pilot gas valve will open and the blower will begin running.

b.Heater will operate until call for heat is satis- fied.

Burner Adjustment

This burner assembly does not require any adjust- ments.

Visual Inspection

Flame can be observed through the slot opening above the plenum. Flame color is blue and evenly spread on the top surface of the burner. At least every three months a visual inspection should be made of the burners. In case flame lifting is observed on the burner, check gas pressure on manifold and static pressure in plenum. Gas pressure in manifold should be 3.9 in. WC and static pressure in plenum should be greater than 0.5 in. WC.

Electrical

Be sure that electrical service to the heater has over- load fuse or circuit breaker protection, wire size and connections that comply with all applicable codes.

High/Low Gas Pressure Switch

Pressure switch senses high/low pressure and auto- matically shuts down burner if abnormal pressure exists.

Fig. 30: Gas Pressure Switch

Fig. 31: Low NOx Burner Tray Assembly

Burner Drawer Removal

1.Shut off main electrical power switch to heater.

2.Shut off gas upstream of heater.

3.Remove front door.

4.Disconnect gas line from gas valve.

5.Remove (2) screws that mount burner tray to unit, and (4) screws that secure gas valve to jacket.

6.Disconnect wires that terminate at gas valve.

7.Unscrew (4) screws that secure the control box.

8.Disconnect pilot wire from the ignition module.

9.Disconnect wire harness from the combustion blower.

27

Image 27
Contents Econopak Water Heaters Page Contents Are important but not related to personal injury hazards General Safety Time/Temperature Relationships in ScaldsTemperature Time to Produce Serious Burn Receiving Equipment General SpecificationsTank Clearances InstallationCode Requirements Mounting BaseModel No Sq. in. of Each Free Area Venting ConnectionsOutdoor Models ModelsModels 0260 Indoor ModelsVent Terminal/Indoor Stack Installation Vent Max Model No Connector Horizontal Diameter Length ftVent Pipe Draft Hood Heater Common VentsModel No Nat Pro Gas Supply ConnectionsGas Pressure Regulator Gas Pressure Specifications Type Inches WC Regulator MinSetting Water Connections & System Piping0261 Low NOx WH1 with Pressure Relief Valve Relief ValveElectrical Wiring Standing Pilot Model Wiring DiagramsIntermittent Ignition Device IID Model Intermittent Ignition Device IID Models 0330 Intermittent Ignition Device IID Model 0261 Low NOx Intermittent Ignition Device IID Models 0331 & 0401 Low NOx Servicing Procedures Start-up ProceduresSequence of Operation Honeywellpilot Robertshaw Pilot System Shut Down Procedure For Automatic Ignition ModelsFor Robertshaw Gas Valve Turn gas control To Turn Off Gas To Appliance Testing the Ignition Safety Shut-offBurners Inspection ProceduresControls Low NOx Heaters-ModelsVisual Inspection Burner AdjustmentHigh/Low Gas Pressure Switch OperationRepair Section Heat Exchanger Re-assembly Heat Exchanger RemovalCombustion Chamber Removal Causes TroubleshootingPiping Intermittent Pilot System- Honeywell S8600 Electrical Electronic Ignition IIDElectrical Standing Pilot Adjustments & Replacement of Components Procedure for Cleaning Flue Gas Passage Ways Circulator ReplacementControl Well Replacement Tube Replacement ProcedureLimitedpartswarrantyeconopakwaterheaters Page Page