INSTALLATION

Code Requirements

Installation must be in accordance with local codes, or, in the absence of local codes, with the latest editions of the National Fuel Gas Code, ANSI Z223.1,/NFPA 54, and the National Electrical Code, ANSI/NFPA 70. In Canada installations must conform with the current CAN/CSA B149 and the Canadian Electrical Code Part 1 CSA C22.2 No.1.

Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Heaters, CSD- 1.

Mounting Base

This heater should be mounted on a level, non-com- bustible surface. Heater must not be installed on carpeting. This heater can be installed on a com- bustible surface only when the appropriate listed floor shield base is provided. An optional listed floor shield base is available for factory installation with the heater on all indoor models.

NOTE: The heater should be located in an area where water leakage will not result in damage to the area adjacent to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.

In addition, the heater shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).

Clearances

 

Minimum Distance

Heater Side

from Combustible

 

Surfaces

 

 

Floor

Combustible*

 

 

Front

Alcove**

 

 

Back

12 in.

 

 

Right

12 in.

 

 

Left

12 in.

 

 

Top (Indoor)

39 in.

 

 

Top (Outdoor)

Unobstructed

 

 

Flue Vent

6 in.

 

 

*Except for carpeted flooring, heaters are certified for installation on combustible floors, when equipped with listed floor shield base. **A front clearance of at least 24 in. is recommended for adequate service of burner-tray and controls.

Table C: Minimum Clearances from Combustible

Surfaces

Combustion & Ventilation Air

(Indoor models only)

WARNING: Air supply to the heater room must not be affected by mechanical exhaust vents located in other parts of the house, such as kitchen or bathroom fans, or attic blowers. Mechanical exhaust vents may create a negative pressure condition in the heater room that can become a hazard of asphyxiation, explosion or fire.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater. Measures must be taken to prevent the entry of corrosive chemical fumes to the combustion and ventilation air supply. Such chemicals include, but are not limited to, chlorinated and/or fluorinated hydrocarbons such as found in refrigerants, aerosol propellants, dry-cleaning fluids, degreasers, and paint removers. Other harmful elements may come from bleaches, air fresheners, or mastics. Vapors from these types of products can form corrosive acid compounds when burned in a gas flame. The resulting acid condensate can damage or substantially reduce the life of the heater. It may be necessary to provide outside air directly to the heater in order to avoid this problem.

8

Image 8
Contents Econopak Water Heaters Page Contents Are important but not related to personal injury hazards Temperature Time to Produce Serious Burn General SafetyTime/Temperature Relationships in Scalds General Specifications Receiving EquipmentTank Installation Code RequirementsMounting Base ClearancesVenting Connections Outdoor ModelsModels Model No Sq. in. of Each Free AreaIndoor Models Models 0260Vent Max Model No Connector Horizontal Diameter Length ft Vent Terminal/Indoor Stack InstallationCommon Vents Vent Pipe Draft Hood HeaterGas Supply Connections Model No Nat ProGas Pressure Specifications Type Inches WC Regulator Min SettingWater Connections & System Piping Gas Pressure RegulatorRelief Valve 0261 Low NOx WH1 with Pressure Relief ValveElectrical Wiring Wiring Diagrams Standing Pilot ModelIntermittent Ignition Device IID Model Intermittent Ignition Device IID Models 0330 Intermittent Ignition Device IID Model 0261 Low NOx Intermittent Ignition Device IID Models 0331 & 0401 Low NOx Sequence of Operation Servicing ProceduresStart-up Procedures Honeywellpilot Robertshaw Pilot For Robertshaw Gas Valve Turn gas control System Shut Down ProcedureFor Automatic Ignition Models Testing the Ignition Safety Shut-off To Turn Off Gas To ApplianceInspection Procedures ControlsLow NOx Heaters-Models BurnersBurner Adjustment High/Low Gas Pressure SwitchOperation Visual InspectionRepair Section Combustion Chamber Removal Heat Exchanger Re-assemblyHeat Exchanger Removal Troubleshooting CausesPiping Electrical Electronic Ignition IID Intermittent Pilot System- Honeywell S8600Electrical Standing Pilot Adjustments & Replacement of Components Circulator Replacement Control Well ReplacementTube Replacement Procedure Procedure for Cleaning Flue Gas Passage WaysLimitedpartswarrantyeconopakwaterheaters Page Page