Raypak 0042B, 0066B, 0180B Gas Supply Connections, Gaspressure, Water Connections & System Piping

Page 11
GAS SUPPLY CONNECTIONS

GAS SUPPLY CONNECTIONS

The inlet gas connection of the boiler gas valve is 1/2". Provide an adequate gas piping supply line no smaller than 1/2", according to the chart below:

Maximum Equivalent Pipe Length (Feet)

Gas piping must have a sediment trap ahead of the boiler gas controls, and a manual shut-off valve located outside the jacket. All gas piping should be tested after installation in accordance with local codes.

Manual

Union

Valve

 

Sediment Trap

Gas Valve

 

Fig. # 8192.0

CAUTION: The boiler and its manual shut-off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 KPA). Dissipate test pressure in the gas supply line before reconnecting the boiler and its manual shut-off valve to gas supply line. FAILURE TO FOLLOW THIS PROCE-

DURE MAY DAMAGE THE GAS VALVE. OVER PRES- SURED GAS VALVES ARE NOT COVERED BY WAR- RANTY. The boiler and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use open flame.

NOTE: Do not use teflon tape on gas line pipe thread.

Aflexible sealant suitable for use with Natural and Propane gases is recommended.

These boilers are also certified to operate on propane gas, when equipped with the combination gas valve and orifices (pilot and main burners) sized for propane gas.

GASPRESSURE

 

 

 

Inches

W.C.

Regulator

 

Min.

Max.

Setting

Natural

7.0

14.0

3.5

Propane

12.0

14.0

11.0

The gas valve is provided with pressure taps to measure gas pressure upstream of the gas valve and downstream which is the same as the manifold pres- sure.

WATER CONNECTIONS & SYSTEM PIPING

The pipe size for water connections is shown on page 3. Typical piping systems are shown on pages 12 to 14.

The boiler is supplied with a circulator and built-in bypass as standard to ensure the required minimum water flow in the boiler. The bypass on models H-0135 and H-0180 is provided with an adjustable valve that is factory-set in the full open position. The handle is shipped loose. The full open position is appropriate for most systems, and ensures adequate flow through the boiler. If system flow is inadequate, (indicated by excessive temperature drop through the system) the bypass valve can be throttled slightly. Care must be taken against over -throttling which may lead to inadequate flow through the boiler and boiler harmonics (a humming sound from the heat exchanger). If adequate system flow cannot be obtained without causing harmonics, an additional pump is required. The factory-mounted circulator will provide adequate water flow for systems designed at a 20°F temperature drop, and system pressure drop or head not exceeding that which is shown below.

When the total system head exceeds the available head pressures, a primary/secondary pumping system is recommended.

The minimum boiler operating temperature should be 105°F. When operating at low tempera- ture applications, GASPRESSURET (temperature rise) must be 20°F or less.

Propylene glycol solution is commonly used in the heating system when freeze protection is required. This will affect the system design and pump performance. As a rule of thumb, 50% solution of propylene glycol will require the system flow (GPM) to increase by 14%, and the system head (Ft/Wtr) by 23% in order to maintain the same heat transfer load.

11

Image 11
Contents INSTALLATION AND OPERATING INSTRUCTIONS FOR YOUR SAFETYRaythermTM Type H RESIDENTIAL BOILERS Models 0042B, 0066B,0090B 0135B, 0180BSERVICING PROCEDURES ContentsGENERAL SPECIFICATIONS INSTALLATION PROCEDURESRECEIVING EQUIPMENT GENERAL SPECIFICATIONSCLEARANCEREQUIREMENTS 3. INSTALLATION PROCEDURESCODE REQUIREMENTS MOUNTING BASEVENTING CONNECTIONS COMMON VENTS VENT DAMPER INSTALLATION Hole in Vent Damper Blade Closed Position FLAIR DAMPER VENT DAMPER OPERATIONVENT DAMPER WIRING DIAGRAM WATER CONNECTIONS & SYSTEM PIPING GAS SUPPLY CONNECTIONSGASPRESSURE SINGLE-ZONEPIPING PIPING DIAGRAMSAIR SCOOP DIAPHRAGM EXPANSION FEED TANK VALVE ZONE HEATING WITH INDIRECT DOMESTICHOT WATER SUPPLY ZONE VALVES HEATINGUNITSMULTIPLE ZONES WITH ZONE VALVES MULTIPLE ZONES WITH CIRCULATORSWIRING DIAGRAM KEY ELECTRICAL WIRINGWIRING DIAGRAMS Page Page Fig. # 2228e WIRING DIAGRAM Single-ZoneTaco ValveWIRING DIAGRAM Dual-ZoneTaco Valve WIRING DIAGRAM Dual-ZoneHoneywell ValveFig. #2233e Fig. #2234e WIRING DIAGRAM System with 3 Zone PumpsWIRING DIAGRAM: Power Vent System w/ Zone Valve Fig. #2232eFig. #2223.2e WIRING DIAGRAM Primary/Secondary Pumping SystemHoneywell Zone Valve Note Low water cut-offLWCO and system switch supplied by others GENERAL LOCATION OF CONTROLS SERVICING PROCEDURESChecking the Circulator START-UPPROCEDURES Lighting the BoilerFor Standing Pilot Models Filling the SystemFOR AUTOMATIC IGNITION MODELS HONEYWELL PILOTROBERTSHAW PILOT TO TURN OFF GAS TO THE BOILER ModelsFor Robertshaw valve SHUT-DOWNPROCEDURETO TURN OFF GAS TO BOILER 3.For Honeywell valveFOR AUTOMATIC IGNITION SYSTEMS INSPECTIONSCHEDULE INSPECTION PROCEDURES BURNERSSAFE SHUT-DOWNTESTS LIMIT ACTION FLAME FAILUREREPAIRPROCEDURES RAYPAK TUBE CLEANING KITHEAT EXCHANGER RE-ASSEMBLY IMPORTANT NOTICE TROUBLESHOOTING GUIDEPROBLEM SOLUTIONS10Defective ignition module or defective gas valve DANGER - SHOCK HAZARD ADJUSTMENT/REPLACEMENTOF COMPONENTSRAYPAK, INC 2151 Eastman Avenue Oxnard, CA REPLACEMENT PARTS LISTPage Page Page PARTS REPLACEMENT LIMITED PARTS WARRANTYHEAT EXCHANGER WARRANTY ADDITIONAL WARRANTY EXCLUSIONS