REPLACEMENT PARTS LIST

9.Fast-Response Temperature Sensor Module Replacement

a)Shut-off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)Disconnect wiring to the board.

d)Carefully pull out the control board from the nylon pin supports.

e)Reverse above procedure to re-install.

10.Fast-Response Temperature Sensor Probe Replacement

a)Shut-off electrical power to the boiler.

b)Shut-off water supply to the boiler and open drain valve to remove water to the sensor probe level.

c)Remove control cover screws and open control compartment.

d)Disconnect wire leads from control board.

e)Remove upper access panel.

f)Remove sensor probe from in/out header.

g)Reverse above procedure to re-install.

11.Circulator Replacement

a)Shut-off electrical power to the boiler.

b)Shut-off water supply and open drain valve to remove water in the piping at the pump level.

CAUTION: To avoid damage to electrical components keep water from getting into the control compartments and gas valve.

c)Disconnect wiring and conduit connections to the pump.

d)Disconnect the bypass tube connections to the inlet flange.

e)Remove the nuts and bolts at the inlet and outlet flanges. Remove old gaskets.

f)Remove the pump.

g)Reverse the above procedure to re-install. Use new gaskets and make sure they are seated properly when tightening the nuts and bolts.

12.2-Stage Controller (Models 90, 135 & 180)

a)Shut-off electrical power to the boiler.

b)Remove control cover screws and open con- trol compartment.

c)The control is factory set at 160°F. To adjust to another setting, use a small screw driver

and turn dial clockwise

to lower the

temperature or counter-clockwise

to

raise the setting.

 

 

d)To replace the stage controller, disconnect the wiring connections.

e)Remove screws (2) holding the staged controller.

f)Remove upper access panel.

g)Remove the wedge or retaining clip holding the sensing bulb in the control well in the in/ out header.

h)Pull out the sensing bulb carefully from the control well.

i)Remove the stage control with capillary from unit.

j)Reverse above procedure to re-install.

REPLACEMENT PARTS LIST

NOTE: To supply the correct part it is important that you supply the model number, serial number and type of gas when applicable.

Any part returned for replacement under standard company warranties must be properly tagged with Raypak return parts tag, completely filled in with the heater serial number, model number etc., and shipped to Raypak freight prepaid.

If determined defective by Raypak and within war- ranty, the part will be returned in kind or equal substitu- tion, freight collect. Credit will not be issued.

RAYPAK, INC.

2151 Eastman Avenue

Oxnard, CA 93030

34

Image 34
Contents 0042B, 0066B,0090B 0135B, 0180B FOR YOUR SAFETYRaythermTM Type H RESIDENTIAL BOILERS Models INSTALLATION AND OPERATING INSTRUCTIONSINSTALLATION PROCEDURES ContentsGENERAL SPECIFICATIONS SERVICING PROCEDURESGENERAL SPECIFICATIONS RECEIVING EQUIPMENTMOUNTING BASE 3. INSTALLATION PROCEDURESCODE REQUIREMENTS CLEARANCEREQUIREMENTSVENTING CONNECTIONS COMMON VENTS VENT DAMPER INSTALLATION Hole in Vent Damper Blade Closed Position VENT DAMPER OPERATION FLAIR DAMPERVENT DAMPER WIRING DIAGRAM GASPRESSURE GAS SUPPLY CONNECTIONSWATER CONNECTIONS & SYSTEM PIPING PIPING DIAGRAMS SINGLE-ZONEPIPINGZONE VALVES HEATINGUNITS ZONE HEATING WITH INDIRECT DOMESTICHOT WATER SUPPLY AIR SCOOP DIAPHRAGM EXPANSION FEED TANK VALVEMULTIPLE ZONES WITH CIRCULATORS MULTIPLE ZONES WITH ZONE VALVESELECTRICAL WIRING WIRING DIAGRAM KEYWIRING DIAGRAMS Page Page WIRING DIAGRAM Dual-ZoneHoneywell Valve WIRING DIAGRAM Single-ZoneTaco ValveWIRING DIAGRAM Dual-ZoneTaco Valve Fig. # 2228eFig. #2232e WIRING DIAGRAM System with 3 Zone PumpsWIRING DIAGRAM: Power Vent System w/ Zone Valve Fig. #2233e Fig. #2234eHoneywell Zone Valve WIRING DIAGRAM Primary/Secondary Pumping SystemFig. #2223.2e Note Low water cut-offLWCO and system switch supplied by others SERVICING PROCEDURES GENERAL LOCATION OF CONTROLSFilling the System START-UPPROCEDURES Lighting the BoilerFor Standing Pilot Models Checking the CirculatorTO TURN OFF GAS TO THE BOILER Models HONEYWELL PILOTROBERTSHAW PILOT FOR AUTOMATIC IGNITION MODELS3.For Honeywell valve SHUT-DOWNPROCEDURETO TURN OFF GAS TO BOILER For Robertshaw valveFOR AUTOMATIC IGNITION SYSTEMS FLAME FAILURE INSPECTION PROCEDURES BURNERSSAFE SHUT-DOWNTESTS LIMIT ACTION INSPECTIONSCHEDULERAYPAK TUBE CLEANING KIT REPAIRPROCEDURESHEAT EXCHANGER RE-ASSEMBLY SOLUTIONS TROUBLESHOOTING GUIDEPROBLEM IMPORTANT NOTICE10Defective ignition module or defective gas valve ADJUSTMENT/REPLACEMENTOF COMPONENTS DANGER - SHOCK HAZARDREPLACEMENT PARTS LIST RAYPAK, INC 2151 Eastman Avenue Oxnard, CAPage Page Page ADDITIONAL WARRANTY EXCLUSIONS LIMITED PARTS WARRANTYHEAT EXCHANGER WARRANTY PARTS REPLACEMENT
Related manuals
Manual 40 pages 10.3 Kb