Raypak 0066B, 0180B, 0042B manual Heat Exchanger Re-Assembly

Page 30
HEAT EXCHANGER RE-ASSEMBLY

6.Remove combustion chamber clips at the four corners of the heat exchanger.

7.Lift heat exchanger straight up using caution not to damage refractory.

Fig# 9337

HEAT EXCHANGER RE-ASSEMBLY

1.Heat exchanger water header O-rings should be replaced with new ones.

2.Install in/out and return water headers and

install header retainer nuts and torque nuts evenly.

3.Replace "V" baffles.

4.Install thermostat sensing bulbs in header wells and replace bulb retaining clips.

5.Install inlet and return pipes in water headers using pipe thread sealant.

6.Install water pressure relief valve, flow switch, and low water cut-off devices if so equipped.

7.Open water supply and return shut-off valves. Fill boiler and water piping system with water. Check

boiler and piping system for leaks at full line pres- sure. Run system circulating pump for a minimum of 1/2 hour with boiler shut off.

8.Shut down entire system and vent all radiation units and high points in system piping. Check all strain- ers for debris. Expansion tank water level should be at the 1/4 mark and the balance of the tank filled with air (when using Air-X-Tank).

9.Install flue collector, jacket top and inspection pan- els. Install top holding screws. Install draft diverter and vent piping if so equipped.

10.If gas piping was disconnected, reconnect gas piping system and check for leakage using a soap solution.

11.Check for correct water pressure and water level in the system. Make sure that system pump operates immediately on the call for heat. The system is ready for operation.

12.Within two (2) days of start-up, recheck all air vents and expansion tank levels.

COMBUSTION CHAMBER REMOVAL

To remove combustion chamber you must first have removed the heat exchanger. Unbolt metal com- bustion chamber retainer from top and remove com- bustion chamber panels individually.

30

Image 30
Contents 0042B, 0066B,0090B 0135B, 0180B FOR YOUR SAFETYRaythermTM Type H RESIDENTIAL BOILERS Models INSTALLATION AND OPERATING INSTRUCTIONSINSTALLATION PROCEDURES ContentsGENERAL SPECIFICATIONS SERVICING PROCEDURESGENERAL SPECIFICATIONS RECEIVING EQUIPMENTMOUNTING BASE 3. INSTALLATION PROCEDURESCODE REQUIREMENTS CLEARANCEREQUIREMENTSVENTING CONNECTIONS COMMON VENTS VENT DAMPER INSTALLATION Hole in Vent Damper Blade Closed Position VENT DAMPER OPERATION FLAIR DAMPERVENT DAMPER WIRING DIAGRAM GAS SUPPLY CONNECTIONS GASPRESSUREWATER CONNECTIONS & SYSTEM PIPING PIPING DIAGRAMS SINGLE-ZONEPIPINGZONE VALVES HEATINGUNITS ZONE HEATING WITH INDIRECT DOMESTICHOT WATER SUPPLY AIR SCOOP DIAPHRAGM EXPANSION FEED TANK VALVEMULTIPLE ZONES WITH CIRCULATORS MULTIPLE ZONES WITH ZONE VALVESELECTRICAL WIRING WIRING DIAGRAM KEYWIRING DIAGRAMS Page Page WIRING DIAGRAM Dual-ZoneHoneywell Valve WIRING DIAGRAM Single-ZoneTaco ValveWIRING DIAGRAM Dual-ZoneTaco Valve Fig. # 2228eFig. #2232e WIRING DIAGRAM System with 3 Zone PumpsWIRING DIAGRAM: Power Vent System w/ Zone Valve Fig. #2233e Fig. #2234eWIRING DIAGRAM Primary/Secondary Pumping System Honeywell Zone ValveFig. #2223.2e Note Low water cut-offLWCO and system switch supplied by others SERVICING PROCEDURES GENERAL LOCATION OF CONTROLSFilling the System START-UPPROCEDURES Lighting the BoilerFor Standing Pilot Models Checking the CirculatorTO TURN OFF GAS TO THE BOILER Models HONEYWELL PILOTROBERTSHAW PILOT FOR AUTOMATIC IGNITION MODELS3.For Honeywell valve SHUT-DOWNPROCEDURETO TURN OFF GAS TO BOILER For Robertshaw valveFOR AUTOMATIC IGNITION SYSTEMS FLAME FAILURE INSPECTION PROCEDURES BURNERSSAFE SHUT-DOWNTESTS LIMIT ACTION INSPECTIONSCHEDULERAYPAK TUBE CLEANING KIT REPAIRPROCEDURESHEAT EXCHANGER RE-ASSEMBLY SOLUTIONS TROUBLESHOOTING GUIDEPROBLEM IMPORTANT NOTICE10Defective ignition module or defective gas valve ADJUSTMENT/REPLACEMENTOF COMPONENTS DANGER - SHOCK HAZARDREPLACEMENT PARTS LIST RAYPAK, INC 2151 Eastman Avenue Oxnard, CAPage Page Page ADDITIONAL WARRANTY EXCLUSIONS LIMITED PARTS WARRANTYHEAT EXCHANGER WARRANTY PARTS REPLACEMENT