Lenox Elite Series XP14 Units HEAT PUMPS, 50677201 installation instructions

Page 27

APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND

ADD CHARGE VALUES

Listed below are the approved matched system

Subcooling values listed in the following tables are based

components (air handlers and indoor coils), targeted

on outdoor ambient air temperature of:

 

 

subcooling and add charge values for the XP14. This

S 60°F (15.5°C) and above for cooling mode

information is also listed on the unit charging sticker

 

 

 

 

 

located on the outdoor unit access panel.

 

S 59°F (15.0°C) and below for heating mode.

 

Table 3. HFC−410A Temperature (°F) − Pressure (Psig)

 

 

 

 

 

 

 

 

 

 

 

°F

°C

 

Psig

°F

°C

 

Psig

 

−40

−40.0

 

11.6

60

15.6

 

170

 

−35

−37.2

 

14.9

65

18.3

 

185

 

−30

−34.4

 

18.5

70

21.1

 

201

 

−25

−31.7

 

22.5

75

23.9

 

217

 

−20

−28.9

 

26.9

80

26.7

 

235

 

−15

−26.1

 

31.7

85

29.4

 

254

 

−10

−23.3

 

36.8

90

32.2

 

274

 

−5

−20.6

 

42.5

95

35.0

 

295

 

0

−17.8

 

48.6

100

37.8

 

317

 

5

−15.0

 

55.2

105

40.6

 

340

 

10

−12.2

 

62.3

110

43.3

 

365

 

15

−9.4

 

70.0

115

46.1

 

391

 

20

−6.7

 

78.3

120

48.9

 

418

 

25

−3.9

 

87.3

125

51.7

 

446

 

30

−1.1

 

96.8

130

54.4

 

476

 

35

1.7

 

107

135

57.2

 

507

 

40

4.4

 

118

140

60.0

 

539

 

45

7.2

 

130

145

62.8

 

573

 

50

10.0

 

142

150

65.6

 

608

 

55

12.8

 

155

 

 

 

 

 

Table 4. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG

IMPORTANT

Use table 4 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in instal- lations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.

Vapor Pressure

Model

 

 

Heating

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

Number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ºF (ºC)*

20

30

40

50

60

65

70

75

 

80

85

90

95

100

105

110

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−018

67

83

100

118

137

145

145

146

 

147

148

149

151

151

153

154

155

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−024

58

72

88

105

123

139

140

142

 

143

144

145

145

146

147

147

148

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−030

55

69

84

102

122

135

136

138

 

140

141

143

144

145

147

148

149

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−036

62

76

91

106

124

135

137

139

 

141

143

145

146

148

150

151

153

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−042

58

73

89

108

130

127

129

131

 

132

134

136

137

139

140

141

142

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−048

60

75

90

105

121

136

137

138

 

139

140

141

142

143

144

146

147

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−060

56

70

84

99

114

132

133

134

 

135

137

138

139

141

142

143

144

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ºF (ºC)*

20

30

40

50

60

65

70

75

 

80

85

90

95

100

105

110

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−018

272

287

305

321

339

242

259

279

 

302

326

351

376

406

433

462

498

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−024

281

295

309

324

340

243

262

281

 

302

325

348

373

399

426

454

483

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−030

274

286

299

313

327

250

268

288

 

308

330

352

376

400

426

452

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−036

287

304

322

342

365

230

248

268

 

288

311

334

359

385

412

441

471

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−042

293

335

368

394

411

215

234

254

 

275

298

321

346

371

398

426

455

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−048

282

299

316

334

353

219

237

256

 

277

298

321

344

369

395

422

450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−060

266

285

309

337

369

222

241

262

 

283

306

330

354

380

406

434

463

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Temperature of the air entering the outside coil.

Page 27

XP14 SERIES

Image 27
Contents Table of Contents Shipping and Packing ListGeneral TOP View Unit Dimensions Inches mmModel Number Identification 14 −036 − 230 − Side ViewPLUMBING, Switches Sensor Components Typical Unit Parts ArrangementControl Panel Caps and Fasteners Torque Requirements Operating Gauge Set and Service Valves11 12 Method Method 2 Limitations Recovering Refrigerant from Existing System1DISCONNECT Power 3RECOVERING RefrigerantNew Outdoor Unit Placement Detail D Slab Side Mounting Detail a Outside Unit PlacementUsing Feet Extenders Elevated Slab MountingRemoving and Installing Panels Louvered Panel InstallationLouvered Panel Removal Adding Polyol Ester OIL Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Line Set RequirementsRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 2CAP and Core Removal 1CUT and DeburPreparation for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SET2CONNECT Gauges and Equipment for Flushing Procedure Equalizer Line Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationLeak Test Line Set and Indoor Coil Manifold Gauge Set Connections for Leak TestingEvacuating Line Set and Indoor Coil Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat ElectricalTypical Unit Wiring Diagram Typical Factory Wiring Copeland Compressor Typical Factory Wiring Interlink Compressor Connect Manifold Gauge SET and WEIGH−IN Charge Unit Start−UpUnit START−UP Leak CHECK, Repair and EvacuateConnections for Optimizing System Charge Calculating System Charge for Outdoor Unit Void of ChargeRefrigerant Charge per Line Set Length Optimizing System Refrigerant Charge Adjusting Indoor AirflowOptimizing Procedure Temperature rise FSATº LIQº SCº = Normal Operating Pressures − Liquid +10 and Vapor +5 Psig CBX32MV−018/024 CX34−31 Defrost Control CMC1 Defrost SystemHomeowner MaintenanceDefrost Control CMC1 Diagnostic LED DealerXP14 Series Sequence of Operation Thermostat Start−Up and Performance ChecklistInstaller City Job Name Job no Date Job Location City