Lenox 50677201 Recovering Refrigerant from Existing System, 1DISCONNECT Power, Method

Page 6

Recovering Refrigerant from Existing System

1DISCONNECT POWER

Disconnect all power to the existing outdoor unit at the disconnect switch and/or main fuse box/breaker panel.

MAIN FUSE

BOX/BREAKER

PANEL

DISCONNECT

SWITCH

2CONNECT MANIFOLD GAUGE SET Connect a manifold gauge set, clean recovery cylinder and a recovery machine to the service ports of the existing unit.

NOTE recovery machine instructions to make the correct manifold gauge set connections for recovery refrigerant. The illustration below is a typical connection.

MANIFOLD GAUGES

RECOVERY MACHINE

LOW HIGH

3RECOVERING REFRIGERANT

CLEAN RECOVERY

OUTDOOR UNIT

CYLINDER

 

Remove existing HCFC−22 refrigerant using one of the following procedures:

METHOD 1:

METHOD 2 LIMITATIONS

Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.

Recover all HCFC−22 refrigerant from the existing system using a recovery machine and clean recovery cylinder. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.

METHOD 2:

Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.

Perform the following task:

AStart the existing HCFC−22 system in the cooling mode and close the liquid line valve.

BUse the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system.

NOTE

ensure complete refrigerant evacuation.

CWhen the low side system pressures reach 0 psig, close the vapor line valve.

DCheck gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.

NOTEMethod 2, the listed devices below could prevent full system charge recovery into the outdoor unit:

SOutdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.

SCompressor can stop pumping due to tripped internal pressure relief valve.

SCompressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)

Once the compressor can not pump down to a lower pressure due to any of the above mentioned system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.

Figure 4. Refrigerant Recovery

IMPORTANT

The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.

Failure to follow this warning may result in personal injury or death.

506728−01

Page 6

Image 6
Contents Table of Contents Shipping and Packing ListGeneral Side View Unit Dimensions Inches mmModel Number Identification 14 −036 − 230 − TOP ViewPLUMBING, Switches Sensor Components Typical Unit Parts ArrangementControl Panel Operating Gauge Set and Service Valves Caps and Fasteners Torque Requirements11 12 3RECOVERING Refrigerant Recovering Refrigerant from Existing System1DISCONNECT Power Method Method 2 LimitationsNew Outdoor Unit Placement Elevated Slab Mounting Detail a Outside Unit PlacementUsing Feet Extenders Detail D Slab Side MountingRemoving and Installing Panels Louvered Panel InstallationLouvered Panel Removal Line Set Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1CUT and Debur 2CAP and Core Removal6BRAZE Line SET Wrap Service ValvesFlow Nitrogen Preparation for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Sensing Bulb Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Equalizer Line InstallationManifold Gauge Set Connections for Leak Testing Leak Test Line Set and Indoor CoilEvacuating Line Set and Indoor Coil Evacuating Line Set and Indoor CoilElectrical Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC TransformerTypical Unit Wiring Diagram Typical Factory Wiring Copeland Compressor Typical Factory Wiring Interlink Compressor Leak CHECK, Repair and Evacuate Unit Start−UpUnit START−UP Connect Manifold Gauge SET and WEIGH−IN ChargeConnections for Optimizing System Charge Calculating System Charge for Outdoor Unit Void of ChargeRefrigerant Charge per Line Set Length Temperature rise F Adjusting Indoor AirflowOptimizing Procedure Optimizing System Refrigerant ChargeSATº LIQº SCº = Normal Operating Pressures − Liquid +10 and Vapor +5 Psig CBX32MV−018/024 CX34−31 Defrost System Defrost Control CMC1Dealer MaintenanceDefrost Control CMC1 Diagnostic LED HomeownerXP14 Series Job Name Job no Date Job Location City Start−Up and Performance ChecklistInstaller City Sequence of Operation Thermostat