Lenox 50677201 Caps and Fasteners Torque Requirements, Operating Gauge Set and Service Valves

Page 4

Caps and Fasteners Torque Requirements

When servicing or repairing HVAC equipment and components, ensure the fasteners are appropriately tightened. Table 1 list torque values for various caps and fasteners.

Table 1. Torque Requirements

Parts

Recommended Torque

 

 

 

Service valve cap

8 ft.− lb.

11 NM

 

 

 

Sheet metal screws

16 in.− lb.

2 NM

 

 

 

Machine screws #10

28 in.− lb.

3 NM

 

 

 

Compressor bolts

90 in.− lb.

10 NM

 

 

 

Gauge port seal cap

8 ft.− lb.

11 NM

 

 

 

Operating Gauge Set and Service Valves

IMPORTANT

To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted

BTo close rotate stem clockwise 90°.

TO INDOOR UNIT

BALL (SHOWN CLOSED)

2 VALVE STEM

SERVICE PORT

SERVICE PORT CORE

SERVICE PORT CAP

TO OUTDOOR UNIT

REMOVE

 

1 STEM CAP

Figure 2. Operating Ball−Type Service Valve

ANGLE−TYPE SERVICE VALVE

1.Remove stem cap with an appropriately sized wrench.

2.Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open the service valve.

snugly over the cap before tightening.

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold gauge set that features low−loss anti−blow back fittings.

Manifold gauge set used for HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The manifold gauges should be rated for:

S High side

square inch gauge (psig)

SERVICE PORT CAP

SERVICE PORT CORE

SERVICE PORT

CORE

TO INDOOR

UNIT

TO OUTDOOR UNIT

(VALVE STEM SHOWN OPEN)

INSERT HEX WRENCH HERE

STEM CAP

S

Low side sig with

 

dampened speed to 500 psig

S

Manifold gauge set hoses must be rated for use to 800

 

psig of pressure with a 4000 psig burst rating.

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for refrigerant recovery, flushing, leak testing, evacuating, weighing in refrigerant and optimizing system charge.

Each valve is equipped with a service port which has a factory−installed valve core. Figure 3 provides information on how to access and operate both angle− and ball−type service valves.

BALL−TYPE SERVICE VALVE

1.Remove stem cap with an appropriately sized wrench.

2.Use an appropriately sized wrenched to open or close valve.

A To open rotate stem counterclockwise 90°.

When service valve is OPEN, the service port is open to line set, indoor and outdoor unit.

INSERT HEX−HEAD

2 EXTENSION HERE

TO INDOOR

UNIT

TO OUTDOOR

 

UNIT

VALVE STEM

 

 

SHOWN

 

CLOSED

1REMOVE STEM CAP

When service valve stem is in the CLOSED position, the service port is open to the line set and indoor unit.

Figure 3. Operating Angle−Type Service Valve

506728−01

Page 4

Image 4
Contents Shipping and Packing List Table of ContentsGeneral Unit Dimensions Inches mm Model Number Identification 14 −036 − 230 −Side View TOP ViewTypical Unit Parts Arrangement PLUMBING, Switches Sensor ComponentsControl Panel Operating Gauge Set and Service Valves Caps and Fasteners Torque Requirements11 12 Recovering Refrigerant from Existing System 1DISCONNECT Power3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Detail a Outside Unit Placement Using Feet ExtendersElevated Slab Mounting Detail D Slab Side MountingLouvered Panel Installation Removing and Installing PanelsLouvered Panel Removal NEW or Replacement Line SET Installation Using Existing Line SETLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1CUT and Debur 2CAP and Core RemovalWrap Service Valves Flow Nitrogen6BRAZE Line SET Preparation for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Installing New Indoor Metering Device Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationManifold Gauge Set Connections for Leak Testing Leak Test Line Set and Indoor CoilEvacuating Line Set and Indoor Coil Evacuating Line Set and Indoor CoilSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical 24VAC TransformerTypical Unit Wiring Diagram Typical Factory Wiring Copeland Compressor Typical Factory Wiring Interlink Compressor Unit Start−Up Unit START−UPLeak CHECK, Repair and Evacuate Connect Manifold Gauge SET and WEIGH−IN ChargeCalculating System Charge for Outdoor Unit Void of Charge Connections for Optimizing System ChargeRefrigerant Charge per Line Set Length Adjusting Indoor Airflow Optimizing ProcedureTemperature rise F Optimizing System Refrigerant ChargeSATº LIQº SCº = Normal Operating Pressures − Liquid +10 and Vapor +5 Psig CBX32MV−018/024 CX34−31 Defrost System Defrost Control CMC1Maintenance Defrost Control CMC1 Diagnostic LEDDealer HomeownerXP14 Series Start−Up and Performance Checklist Installer CityJob Name Job no Date Job Location City Sequence of Operation Thermostat