Lenox 50677201 Detail a Outside Unit Placement, Elevated Slab Mounting, Using Feet Extenders

Page 8

DETAIL A Outside Unit Placement

Install unit away from windows.

TWO 90° ELBOWS INSTALLED IN LINE SET WILL

REDUCE LINE SET VIBRATION.

DETAIL B

Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.

BUILDING

STRUCTURE

MOUNTING

SLAB

GROUND LEVEL

DETAIL C

 

Elevated Slab Mounting

 

using Feet Extenders

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASE

LEG DETAIL

DETAIL D Slab Side Mounting

#10 1/2" LONG SELF−DRILLING SHEET METAL SCREWS

STABILIZING BRACKET (18 GAUGE

METAL

REQUIRED)

#10 1−1/4" LONG HEX HD SCREW AND FLAT WASHER

Concrete slab plastic anchors (hole drill 1/4")

Wood or plastic slab drill 1/8")

Stabilizing bracket (18 gauge metal right angle as exampled below.

COIL

BASE PAN

CORNER POST

2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER

2" (50.8MM) SCH 40 MALE THREADED ADAPTER

Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.

DETAIL E Deck Top Mounting

DETAIL F Roof Top Mounting

If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated.

PREVAILING WINTER WINDS

WIND BARRIER

INLET AIR

One bracket per side (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner.

SAME FASTENERS AS

SLAB SIDE MOUNTING.

MINIMUM ONE PER SIDE

FOR EXTRA

STABILITY

INLET AIR

INLET AIR

INLET AIR

Figure 6. Placement, Slab Mounting and Stabilizing Unit

506728−01

Page 8

Image 8
Contents General Table of ContentsShipping and Packing List Unit Dimensions Inches mm Model Number Identification 14 −036 − 230 −Side View TOP ViewControl Panel PLUMBING, Switches Sensor ComponentsTypical Unit Parts Arrangement Operating Gauge Set and Service Valves Caps and Fasteners Torque Requirements11 12 Recovering Refrigerant from Existing System 1DISCONNECT Power3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Detail a Outside Unit Placement Using Feet ExtendersElevated Slab Mounting Detail D Slab Side MountingLouvered Panel Removal Removing and Installing PanelsLouvered Panel Installation NEW or Replacement Line SET Installation Using Existing Line SETLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1CUT and Debur 2CAP and Core RemovalWrap Service Valves Flow Nitrogen6BRAZE Line SET Preparation for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Installing New Indoor Metering Device Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationManifold Gauge Set Connections for Leak Testing Leak Test Line Set and Indoor CoilEvacuating Line Set and Indoor Coil Evacuating Line Set and Indoor CoilSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical 24VAC TransformerTypical Unit Wiring Diagram Typical Factory Wiring Copeland Compressor Typical Factory Wiring Interlink Compressor Unit Start−Up Unit START−UPLeak CHECK, Repair and Evacuate Connect Manifold Gauge SET and WEIGH−IN ChargeRefrigerant Charge per Line Set Length Connections for Optimizing System ChargeCalculating System Charge for Outdoor Unit Void of Charge Adjusting Indoor Airflow Optimizing ProcedureTemperature rise F Optimizing System Refrigerant ChargeSATº LIQº SCº = Normal Operating Pressures − Liquid +10 and Vapor +5 Psig CBX32MV−018/024 CX34−31 Defrost System Defrost Control CMC1Maintenance Defrost Control CMC1 Diagnostic LEDDealer HomeownerXP14 Series Start−Up and Performance Checklist Installer CityJob Name Job no Date Job Location City Sequence of Operation Thermostat