Lenox Elite Series XP14 Units HEAT PUMPS, 50677201 Leak Test Line Set and Indoor Coil

Page 17

Leak Test Line Set and Indoor Coil

IMPORTANT

Leak detector must be capable of sensing HFC refrigerant.

CONNECT GAUGE SET

A Connect an HFC−410A manifold gauge set high pressure hose to the

vapor valve service port.

LOW

HIGH

NOTE , the high pressure hose is connected to the liquid

MANIFOLD GAUGE SET

line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.

BWith both manifold valves closed, connect the cylinder of HFC−410A

refrigerant to the center port of the manifold gauge set.

NOTE

HFC−410A container will be replaced by the nitrogen container.

BA

TO VAPOR

SERVICE VALVE (ANGLE OR BALL TYPE)

NITROGENOUTDOOR UNIT

HFC−410A

Figure 13. Manifold Gauge Set Connections for Leak Testing

TEST FOR LEAKS

After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:

1.With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (vapor only).

2.Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure

side of the manifold gauge set. Disconnect the HFC−410A cylinder.

3.Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

4.Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.

5.After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.

6.After leak testing disconnect gauges from service ports.

Page 17

XP14 SERIES

Image 17
Contents General Table of ContentsShipping and Packing List Model Number Identification 14 −036 − 230 − Unit Dimensions Inches mmSide View TOP ViewControl Panel PLUMBING, Switches Sensor ComponentsTypical Unit Parts Arrangement Caps and Fasteners Torque Requirements Operating Gauge Set and Service Valves11 12 1DISCONNECT Power Recovering Refrigerant from Existing System3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Using Feet Extenders Detail a Outside Unit PlacementElevated Slab Mounting Detail D Slab Side MountingLouvered Panel Removal Removing and Installing PanelsLouvered Panel Installation Using Existing Line SET NEW or Replacement Line SET InstallationLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 2CAP and Core Removal 1CUT and DeburFlow Nitrogen Wrap Service Valves6BRAZE Line SET Preparation for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Indoor Expansion Valve Installation Installing New Indoor Metering DeviceSensing Bulb Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Manifold Gauge Set Connections for Leak TestingEvacuating Line Set and Indoor Coil Evacuating Line Set and Indoor Coil2INSTALL Thermostat Size Circuit and Install DisconnectElectrical 24VAC TransformerTypical Unit Wiring Diagram Typical Factory Wiring Copeland Compressor Typical Factory Wiring Interlink Compressor Unit START−UP Unit Start−UpLeak CHECK, Repair and Evacuate Connect Manifold Gauge SET and WEIGH−IN ChargeRefrigerant Charge per Line Set Length Connections for Optimizing System ChargeCalculating System Charge for Outdoor Unit Void of Charge Optimizing Procedure Adjusting Indoor AirflowTemperature rise F Optimizing System Refrigerant ChargeSATº LIQº SCº = Normal Operating Pressures − Liquid +10 and Vapor +5 Psig CBX32MV−018/024 CX34−31 Defrost Control CMC1 Defrost SystemDefrost Control CMC1 Diagnostic LED MaintenanceDealer HomeownerXP14 Series Installer City Start−Up and Performance ChecklistJob Name Job no Date Job Location City Sequence of Operation Thermostat