Lenox 50677201, Elite Series XP14 Units HEAT PUMPS installation instructions Satº Liqº Scº =

Page 26
3. Determine if fan needs adjustment

 

 

 

 

 

 

 

 

 

 

 

DT

 

 

 

 

 

 

 

 

Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of air

 

80

24

24

24

23

23

22

22

 

22

20

19

18

17

16

15

 

entering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry−bulb

78

23

23

23

22

22

21

21

 

20

19

18

17

16

15

14

 

indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

76

22

22

22

21

21

20

19

 

19

18

17

16

15

14

13

 

coil ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

21

21

21

20

19

19

18

 

17

16

16

15

14

13

12

 

 

 

 

 

 

A

 

 

72

20

20

19

18

17

17

16

 

15

15

14

13

12

11

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7019 19 18 18 17 17 16 15 15 14 13 12 11 10

Wet−bulb ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70

1. Determine the desired DT

ature using dry bulb (A) and wet bulb (B). DT is the intersect- ing value of A and B in the table (see triangle).

2. Find temperature drop across coil

bulb entering and leaving air temperatures (A and C). Tem- perature Drop Formula: (TDrop) = A minus C.

ference between

 

 

B

 

C

TDrop

 

 

 

 

 

53º

19º

 

 

 

 

 

 

air flow

air flow

B

DRY

 

 

64º

BULB

 

 

 

All temperatures are

INDOOR

 

COIL

 

expressed in ºF

 

 

 

A 72º

DRY

BULB

WET

BULB

the measured TDrop and the desired DT (TDropDT) is within +3º, no adjustment is needed. See examples: Assume DT =

15 and A temp. = 72º, these C temperatures would necessi- tate stated actions:

TDrop

DT

=

ºF

ACTION

53º

19

15

=

4

Increase the airflow

58º

14

15

=

−1

(within +3º range) no change

62º

10

15

=

−5

Decrease the airflow

4.Adjust the fan speed crease/decrease fan speed.

Changing air flow affects all temperatures; recheck tempera- tures to confirm that the temperature drop and DT are within +3º.

Figure 22. Checking Airflow over Indoor Coil Using Delta−T Formula

USE

COOLING

MODE

60ºF

(15ºC)

USE

HEATING

MODE

SATº

LIQº –

SCº =

1.Check liquid and vapor line pressures. Compare pressures with either second−stage heat or cooling mode normal operating pressures listed in table 4. Table 4 is a general guide and expect minor pressures variations. Significant pressure differences may indicate improper charge or other system problem.

2.Decide whether to use cooling or heating mode based on current outdoor ambient temperature:

AUse COOLING MODE when:

SOutdoor ambient temperature is 60°F (15.5°C) and above.

SIndoor return air temperature range is between 70 to 80°F (21−27°C). This temperature range is what the target subcooling values are base upon in table 5.

If indoor return air temperature is not within reference range, set thermostat to cooling mode and a setpoint of 68ºF (20ºC). This should place the outdoor unit into second−stage (high−capacity) cooling mode. When operating and temperature pressures have stabilized, continue to step 3.

BUse HEATING MODE when:

SOutdoor ambient temperature is 59°F (15.0°C) and below.

SIndoor return air temperature range is between 65−75°F (18−24°C). This temperature range is what the target subcooling values are base upon in table 5.

If indoor return air temperature is not within reference range, set thermostat to heating mode and a setpoint of 77ºF (25ºC). This should place the outdoor unit into second−stage (high−capacity) heating mode. When operating and temperature pressures have stabilized, continue to step 3.

3.Read the liquid line pressure; then find its corresponding temperature pressure listed in table 3 and record it in the SATº space to the left.

4.Read the liquid line temperature; record in the LIQº space to the left.

5.Subtract LIQº temperature from SATº temperature to determine subcooling; record it in SCº space to the left.

6.Compare SCº results with table 5 (either Heating or Cooling mode column), also consider any additional charge required for line set lengths longer than 15 feet and/or unit matched component combinations (Add Charge column).

7.If subcooling value is:

AGREATER than shown for the applicable unit match component, REMOVE refrigerant; BLESS than shown for the applicable unit match component, ADD refrigerant.

8.If refrigerant is added or removed, repeat steps 3 through 6 to verify charge.

9.Close all manifold gauge set valves and disconnect gauge set from outdoor unit.

10.Replace the stem and service port caps and tighten as specified in Operating Service Valves on page .

11.Recheck voltage while the unit is running. Power must be within range shown on the nameplate.

Figure 23. Using HFC−410A Subcooling Method tage (High Capacity)

506728−01

Page 26

Image 26
Contents General Table of ContentsShipping and Packing List Side View Unit Dimensions Inches mmModel Number Identification 14 −036 − 230 − TOP ViewControl Panel PLUMBING, Switches Sensor ComponentsTypical Unit Parts Arrangement Operating Gauge Set and Service Valves Caps and Fasteners Torque Requirements11 12 3RECOVERING Refrigerant Recovering Refrigerant from Existing System1DISCONNECT Power Method Method 2 LimitationsNew Outdoor Unit Placement Elevated Slab Mounting Detail a Outside Unit PlacementUsing Feet Extenders Detail D Slab Side MountingLouvered Panel Removal Removing and Installing PanelsLouvered Panel Installation Line Set Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1CUT and Debur 2CAP and Core Removal6BRAZE Line SET Wrap Service ValvesFlow Nitrogen Preparation for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Sensing Bulb Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Equalizer Line InstallationManifold Gauge Set Connections for Leak Testing Leak Test Line Set and Indoor CoilEvacuating Line Set and Indoor Coil Evacuating Line Set and Indoor CoilElectrical Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC TransformerTypical Unit Wiring Diagram Typical Factory Wiring Copeland Compressor Typical Factory Wiring Interlink Compressor Leak CHECK, Repair and Evacuate Unit Start−UpUnit START−UP Connect Manifold Gauge SET and WEIGH−IN ChargeRefrigerant Charge per Line Set Length Connections for Optimizing System ChargeCalculating System Charge for Outdoor Unit Void of Charge Temperature rise F Adjusting Indoor AirflowOptimizing Procedure Optimizing System Refrigerant ChargeSATº LIQº SCº = Normal Operating Pressures − Liquid +10 and Vapor +5 Psig CBX32MV−018/024 CX34−31 Defrost System Defrost Control CMC1Dealer MaintenanceDefrost Control CMC1 Diagnostic LED HomeownerXP14 Series Job Name Job no Date Job Location City Start−Up and Performance ChecklistInstaller City Sequence of Operation Thermostat