III. BURNER ADJUSTMENT

VICTORY

13

Figure 12. IID System with Honeywell VR8204 or VR8304 Gas Valve

4.The higher* heating value of gas varies substantially for different localities. Consult with Slant/Fin’s Technical Ser- vice Dept. for re-orificing procedures if any of the following apply:

a.Boiler (burner) is overfiring. CAUTION! National Fuel Gas Code (ANSI Z223.1-latest edition) does NOT permit firing at a higher input rate than the input rate indicated on the boiler rating plate in order to avoid hazardous conditions such as explo- sion or carbon monoxide poisoning.

b.Poor higher* heating value of gas is causing the actual input to be substantially lower than the rating plate indication.

*“Higher heating” value of gas is commonly

known as “heating value”.

The gas metered in 3 minutes to obtain rated input for each boiler model, using 1000 Btu/cu.ft. gas, is tabulat- ed in gas rate table.

8.Turn on all electric power to the appliance.

9.Set thermostat to desired setting.

10. If the appliance will not operate, follow the instructions

"To Turn Off Gas To Appliance" and call your service technicianToTurngas OffsupplierGas. to Appliance

1.Set thermostat to lowest setting.

2.Turn off all electric power to the appliance if service is

to be performed.

 

 

3. Turn gas control knob clockwise

 

to “OFF”.

DO NOT force.

 

 

III. BURNER ADJUSTMENT

 

 

A. Adjust gas input rate:

1. Consult gas supplier for higher heating value of gas (Btu/cu.ft.).

2. Set thermostat high enough so that boiler will remain on while checking rate.

3. Measure manifold pressure at 1/8" tapping. Correct manifold pressure for gas used is printed on boiler rating plate. NOTE: Gas pressure may be adjusted by turning pressure regulator screw on combination gas valve (turn clockwise to increase pressure, counterclockwise to decrease pressure).

a. Input for PROPANE is approximately at rating shown on rating plate when manifold pressure is 9-1/2" water column.

b. Input for NATURAL GAS is approximately at rat- ing when manifold pressure is 3-1/2" water col- umn, but should be checked on the gas meter:

Btuh Input = Btu/cu. ft. x cu. ft. metered in 3 min- utes x 20

Example 1:

For 1000 Btu/cu.ft. gas, this becomes: Btuh Input = cu. ft. metered in 3 minutes x 1,000 Btu/cu.ft. x 20

Example 2:

For 1050 Btu/cu.ft. gas, this becomes: Btuh Input = cu. ft. metered in 3 minutes x 1050 Btu/cu.ft. x 20

Boiler rated input in

Cubic Feet Gas Consumption

cu. ft./hr. of 1000 Btu/cu. ft.

1000 Btu/cu. ft. gas, in

Natural Gas

3 minutes, at rated input

33

1.65

60

3.00

90

4.50

120

6.00

150

7.50

180

9.00

B. Main Burners

1.Fire the boiler continuously for at least 15 minutes, to reach burner operating temperature.

2.Observe the flames, all burners. The base of all flame jets should be blue. The tips should be blue shading to orange. NOTE: Dust, disturbed by any movement, will cause bright orange flames. Wait for dust to settle.

3.For one burner, close the air shutter until some of its flame jet tips turn yellow-white, indicating insuffi- cient primary air. Then open shutter until whitish tips disappear completely. Set all burner shutters to the same opening. Observe to make sure that no yellow-white tips appear over any portion of the flame. Small yellow tips at the pilot location are permitted.

NOTE: This adjustment method gives MINIMUM primary air setting for safe combustion. DO NOT attempt to make this adjustment unless burners are at operating temperature. Adjustment should be made with burner access panel in final operating position. Use of a mirror may be helpful to observe flames. Note that burner ports are on top of main burner tube.

C.Main Burner Ignition Checkout and Pilot Adjustment.

1.The pilot flame must not smother or snuff out when tested as follows:

a.Main burner ignition from cold start-repeat.

b.Continued operation of main burner.

c.Main burner ignition with appliance at maximum operating temperature after prolonged operation.

NOTE: Observe operation of the pilot burner with appliance doors in the final operating position. Use of a mirror may be helpful.

Image 13
Contents HOT WATER MODELS V-33THROUGH VictoryFigure 2. Front View Figure 1. Left End ViewFigure 3. Right End View VICTORYVICTORY INSTALLATION REQUIREMENTSNATURAL GAS FIRED BOILER LOCATION BOILER FOUNDATIONReference Table No VICTORY Figure 4. Vent Sealing InstructionsModel/Vent Size VICTORYRequirements NATURAL DRAFT CHIMNEYFigure 6a All vent connector joints must be LIQUID tightALL ITEMS SHOWN BELOW ARE REQUIRED Horizontal Venting 3 IN. All Victory Models Horizontal Venting 3 IN. All Victory Models VICTORYVICTORY Vertical Venting 3 IN. All Victory ModelsVICTORY ELECTRICAL CONTROLS AND WIRINGBOILER ROOM AIR SUPPLY AND VENTILATION VICTORY SAFETY INFORMATIONOPERATING INSTRUCTIONS, BASIC I. FILLING AND VENTING WATER SYSTEMSVICTORY III. BURNER ADJUSTMENTVICTORY CARE AND MAINTENANCEburners as described on page APPENDIX A VICTORYAPPENDIX B Vent System Location and Condensation Drain RequirementsSequence of Operations Wiring DiagramsOne R-845Aneeded for each circulator Pump Zoning system using R845 RelayCOMBINATION CONTROLS WITH T TV Z TERMINALSGENERAL TROUBLESHOOTING GUIDE FOR SERVICEPEOPLE VICTORY IF REPLACEMENT PARTS ARE NEEDEDPIPING A HEATING - COOLING SYSTEM TO A WATER BOILER AND CHILLER