Slant/Fin V-180, V-33 operating instructions Reference Table No

Page 4
Reference Table No. *
VICTORY
For a masonry vitreous tile-lined chimney which is not exposed to the outdoors, use Table 1 in this Slant/Fin manual for venting requirements. DO NOT install this system into an unlined masonry chimney.
If a masonry chimney is exposed to the outdoors on one or more sides below the roof line (exposed chimney), it must be re-lined with a UL LISTED metallic liner system. See Table 2 in this Slant/Fin manual for venting require- ments of metallic re-lined chimneys.
If a Type “B” vent system is used, it must NOT be exposed to the outdoors below the roof line. See Table 2 in this Slant/Fin manual for venting requirements. Vent connectors serving appliances vented by natural draft shall
NOT be connected into any portion of mechanical draft sys- tems operating under positive pressure. Single or multiple appliance venting is shown in Figures 6a and 6b.
All Victory boilers require a condensate drain and drain trap. Vent connectors must be liquid tight.

4

NATURAL DRAFT CHIMNEY AND TYPE “B” VENTING VICTORY boilers are power (fan assisted) vented boilers. All Victory boiler models can be PRESSURE side wall or verti- cally vented by connecting the proper 3" diameter vent to the 3" diameter collar and adapter factory equipped on the Victory boilers. See “HORIZONTAL PRESSURE VENTING” and “VERTICAL PRESSURE VENTING”.

Models V-33 and V-60 can ONLY be pressure vented as described above and must NOT be vented into a chimney or “B” vent.

Models V-90, V-120, V-150 and V-180 may be vented into a natural draft chimney or natural draft “B” vent if the factory equipped 3" diameter flue collar and adapter on the boiler is REMOVED and REPLACED by the 5" diameter flue collar

manufactured by Slant/Fin Corporation and included in the V- If90thethroughboilerV-vent180 shippingis to be installedcra es. (Seeintofiguresa natural6a anddraft6b.) masonry chimney or Type “B” venting, it must be in accordance with National Fuel Gas Code ANSI Z223.1- latest edition, Part 7, Part 11 and Appendix G.

Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined)

 

Chimneys not exposed to the outdoors below the roof line. (5" dia. collar must be used)

Reference Table No. *

 

 

 

 

 

 

 

 

 

 

Appliance

Connector

Requirements*

(ANSI Z223.1)

 

Victory Boilers

Type “B”

1.

Connector diameter must be upsized to 7".

11-3

 

 

(V-90, V-120, V-150 and V-180)

 

2.

Chimney height limits: Min. 15 ft., Max. 30 ft.

 

 

 

Single Appliance

 

3.

Lateral length restriction applies (see table 11-3)

 

 

 

 

 

4.

Internal area of chimney: Min. 50 sq. in.,

 

 

 

 

 

 

Max. 269 sq. in.

 

 

 

 

 

 

 

 

 

 

Victory Boiler

Single-wall

1.

Connector diameter must be upsized to 7".

11-4

 

 

(V-180 only)

 

2.

Chimney height limits: Min. 15 ft., Max. 30 ft.

 

 

 

Single Appliance

 

3.

Max. lateral length may not exceed 2 ft.

 

 

 

 

 

4.

Internal area of chimney: Min. 50 sq. in.,

 

 

 

 

 

 

Max. 269 sq. in.

 

 

 

 

 

 

 

 

 

 

Victory Boilers

Type “B”

1.

See table 11-8 for chimney height and connector

11-8

 

 

(V-90, V-120, V-150 and V-180)

 

 

length restrictions.

 

 

 

plus another gas appliance

 

2.

Connector may have to be upsized to 6" diameter

 

 

 

 

 

 

to meet requirement of 11-8.

 

 

 

 

 

 

 

 

 

 

Victory Boilers

Single-wall

1.

See table 11-9 for chimney height and connector

11-9

 

 

(V-150 and V-180 only)

 

 

length restrictions.

 

 

 

plus another gas appliance

 

2.

Connector may have to be upsized to 6" diameter

 

 

 

 

 

 

to meet requirement of 11-9.

 

 

 

 

 

 

 

 

 

Table 2. Type “B” Venting and Metal-Lined Masonry Chimney

Reference Table No. *

 

 

 

 

UL LISTED MATERIALS ONLY. (5” dia. collar must be used)

 

 

 

 

 

 

 

 

 

 

 

Appliance

Connector

Requirements*

(ANSI Z223.1)

 

 

Victory Boilers

Type “B”

See table 11-1 for minimum and maximum of vent

11-1

 

 

(V-90, V-120, V-150 and V-180)

 

height and lateral length restriction.

 

 

 

Single appliance

 

 

 

 

 

 

Victory Boiler

Single-wall

See table 11-2 for minimum and maximum of vent

11-2

 

 

(V-90, V-120, V-150 and V-180)

 

height and lateral length restriction.

 

 

 

Single appliance

 

 

 

 

 

 

Victory Boilers

Type “B”

1. See table 11-6 for vent height and connector

11-6

 

 

(V-90, V-120, V-150 and V-180)

 

 

length restrictions.

 

 

 

plus another gas appliance

 

2. Connector and vent diameter may have to be in-

 

 

 

 

 

 

creased to 6” or 7” to meet requirement of table 11-6.

 

 

 

 

 

 

 

 

 

Victory Boilers

Single-wall

1. See table 11-7 for vent height and connector

11-7

 

 

(V-120, V-150 and V-180 only)

 

 

length restrictions.

 

 

 

plus another gas appliance

 

2. Connector and vent diameter may have to be

 

 

 

 

 

 

increased to 6” to meet requirement of table 11-7.

 

 

 

 

 

 

 

 

 

* Also see Z223.1 Part 7 and see Part 11 for use of mentioned tables.

Image 4
Contents Victory HOT WATER MODELS V-33THROUGHFigure 1. Left End View Figure 2. Front ViewFigure 3. Right End View VICTORYINSTALLATION REQUIREMENTS VICTORYNATURAL GAS FIRED BOILER LOCATION BOILER FOUNDATIONReference Table No Figure 4. Vent Sealing Instructions VICTORYVICTORY Model/Vent SizeRequirements NATURAL DRAFT CHIMNEYFigure 6a All vent connector joints must be LIQUID tightALL ITEMS SHOWN BELOW ARE REQUIRED Horizontal Venting 3 IN. All Victory Models VICTORY Horizontal Venting 3 IN. All Victory ModelsVertical Venting 3 IN. All Victory Models VICTORYVICTORY ELECTRICAL CONTROLS AND WIRINGBOILER ROOM AIR SUPPLY AND VENTILATION SAFETY INFORMATION VICTORYOPERATING INSTRUCTIONS, BASIC I. FILLING AND VENTING WATER SYSTEMSIII. BURNER ADJUSTMENT VICTORYCARE AND MAINTENANCE VICTORYburners as described on page VICTORY APPENDIX AAPPENDIX B Vent System Location and Condensation Drain RequirementsWiring Diagrams Sequence of OperationsPump Zoning system using R845 Relay One R-845Aneeded for each circulatorCOMBINATION CONTROLS WITH T TV Z TERMINALSGENERAL TROUBLESHOOTING GUIDE FOR SERVICEPEOPLE IF REPLACEMENT PARTS ARE NEEDED VICTORYPIPING A HEATING - COOLING SYSTEM TO A WATER BOILER AND CHILLER