VICTORY | 11 |
|
|
|
|
|
|
|
|
Length |
|
| Gas Flow In Piping |
|
| ||
|
| Iron Pipe Size |
|
| |||
of Pipe |
|
|
|
| |||
in Feet |
|
|
|
|
|
|
|
| 1/2 | 3/4 | 1 |
| |||
|
|
| |||||
10 |
| 132 | 278 | 520 | 1050 | 1600 |
|
20 |
| 92 | 190 | 350 | 730 | 1100 |
|
30 |
| 73 | 152 | 285 | 590 | 890 |
|
40 |
| 63 | 130 | 245 | 500 | 760 |
|
50 |
| 56 | 115 | 215 | 440 | 670 |
|
60 |
| 50 | 105 | 195 | 400 | 610 |
|
70 |
| 46 | 96 | 180 | 370 | 560 |
|
80 |
| 43 | 90 | 170 | 350 | 530 |
|
90 |
| 40 | 84 | 160 | 320 | 490 |
|
100 |
| 38 | 79 | 150 | 305 | 460 |
|
At pressure drop of 0.3 in. water, specific gravity = 0.60.
at test pressures equal to or less than 1/2 PSIG.
D. All gas piping used should be inspected thoroughly for cleanliness before makeup. A sediment trap must be pro- vided, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure
when the boiler or any other appliance is turned on or off.
ELECTRICAL CONTROLS AND WIRING
A. The electrical power to the boiler must be on a separately fused and live circuit.
B. If an external electrical source is utilized, the boiler, when installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA No.
C. Basic control wiring diagrams are given on page 17 and 18. Other control systems may be factory supplied: see User's Information Manual and instructions packed with control system supplied.
D. After placing the boiler in operation, the safety shutoff
device must be tested. See page 14 safety check.
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required to obtain combustion and ventilation. ALL AIR COMES FROM OUTSIDE, directly through wall openings to the boiler or through unsealed openings around windows, doors, etc. in the whole building. When buildings are insulated, caulked and
Figure 10. Air Eliminating System
opening 10"X10" has 100 square inches of area. If fly screen must be used over openings, double the area and inspect and clean the screen frequently.
Openings must never be reduced or closed. If doors or win- dows are used for air supply, they must be locked open. Protect against closure of openings by snow and debris. Inspect frequently.
No mechanical draft exhaust or supply fans are to be used in or near the boiler area.
The flow of combustion and ventilating air to the boiler must WATERnot be obstructedPIPING .
I.CIRCULATING SYSTEMS
A.Packaged water boilers are equipped with a water circu- lating pump, mounted to return the water into the boiler. For some installations, the pump should be on the sup- ply main. See PUMP LOCATION, on page 12.
II.AIR CONTROL SYSTEM
A.
If system pressure needs further control, add an addi- tional tank or install a larger capacity tank.
Locate the tank near the boiler, as illustrated.
An automatic air vent should be installed in the top of the boiler. See illustration.