Slant/Fin V-33, V-180 operating instructions All Items Shown Below Are Required

Page 7
Figure 6a.

VICTORY

7

Figure 6a.

Chimney Venting for V-90, V-120, V-150 and V-180 only.

 

Minimum vent connectors diameter is 5 inches. It may have to be upsized to 6 or 7 inches (see Table 1).

 

Single or multiple appliance venting into chimney using single wall or type “B” metal connectors, must be installed

 

in accordance with National Fuel Gas Code ANSI Z223.1-latest edition, part 7 and 11. See “Chimney and Type “B”

 

Venting” paragraph on page 4 of this manual. DO NOT use galvanized risers and connectors in cool boiler rooms.

 

ALL ITEMS SHOWN BELOW ARE REQUIRED.

 

All vent connector joints must be LIQUID tight.

Figure 6b. Venting with “B” vent or metal-lined chimney for V-90, V-120, V-150 and V-180 only

Minimum vent connectors diameter is 5 inches. It may have to be upsized to 6 or 7 inches (see Table 2). Single or multiple appliance venting into Type “B” double wall metal vent with single or Type “B” metal connectors, must be installed in accordance with National Fuel Gas Code ANSI Z223.1-latest edition, part 7 and 11. DO NOT use galvanized risers and connectors in cool boiler rooms.

ALL ITEMS SHOWN BELOW ARE REQUIRED EXCEPT WHERE OTHERWISE INDICATED. All vent connector joints must be liquid tight.

Image 7
Contents HOT WATER MODELS V-33THROUGH VictoryVICTORY Figure 1. Left End ViewFigure 2. Front View Figure 3. Right End ViewBOILER FOUNDATION INSTALLATION REQUIREMENTSVICTORY NATURAL GAS FIRED BOILER LOCATIONReference Table No VICTORY Figure 4. Vent Sealing InstructionsNATURAL DRAFT CHIMNEY VICTORYModel/Vent Size RequirementsFigure 6a All vent connector joints must be LIQUID tightALL ITEMS SHOWN BELOW ARE REQUIRED Horizontal Venting 3 IN. All Victory Models Horizontal Venting 3 IN. All Victory Models VICTORYVICTORY Vertical Venting 3 IN. All Victory ModelsVICTORY ELECTRICAL CONTROLS AND WIRINGBOILER ROOM AIR SUPPLY AND VENTILATION I. FILLING AND VENTING WATER SYSTEMS SAFETY INFORMATIONVICTORY OPERATING INSTRUCTIONS, BASICVICTORY III. BURNER ADJUSTMENTVICTORY CARE AND MAINTENANCEburners as described on page Drain Requirements VICTORYAPPENDIX A APPENDIX B Vent System Location and CondensationSequence of Operations Wiring DiagramsTERMINALS Pump Zoning system using R845 RelayOne R-845Aneeded for each circulator COMBINATION CONTROLS WITH T TV ZGENERAL TROUBLESHOOTING GUIDE FOR SERVICEPEOPLE BOILER AND CHILLER IF REPLACEMENT PARTS ARE NEEDEDVICTORY PIPING A HEATING - COOLING SYSTEM TO A WATER