VICTORY | 7 |
Figure 6a. | Chimney Venting for |
| Minimum vent connectors diameter is 5 inches. It may have to be upsized to 6 or 7 inches (see Table 1). |
| Single or multiple appliance venting into chimney using single wall or type “B” metal connectors, must be installed |
| in accordance with National Fuel Gas Code ANSI |
| Venting” paragraph on page 4 of this manual. DO NOT use galvanized risers and connectors in cool boiler rooms. |
| ALL ITEMS SHOWN BELOW ARE REQUIRED. |
| All vent connector joints must be LIQUID tight. |
Figure 6b. Venting with “B” vent or
Minimum vent connectors diameter is 5 inches. It may have to be upsized to 6 or 7 inches (see Table 2). Single or multiple appliance venting into Type “B” double wall metal vent with single or Type “B” metal connectors, must be installed in accordance with National Fuel Gas Code ANSI
ALL ITEMS SHOWN BELOW ARE REQUIRED EXCEPT WHERE OTHERWISE INDICATED. All vent connector joints must be liquid tight.