Slant/Fin VSPH-60 Integrated Boiler Control, Normal Operation Status of Indicator Lights LED’S

Page 22

22

VICTORY VSPH Models

a.Input for PROPANE is approximately at rating shown on ating plate when manifold pressure is 9-12" water column

b.Input for NATURAL GAS is approximately at rating when manifold pressure is 3-1/2" water column, but should be checked on the gas meter:

Btuh Input = Btu/cu. ft. metered in 3 minutes x 20

EXAMPLE #1:

For 1000 Btu/cu. ft. gas, this becomes:

Btuh Input = cu. ft. metered in 3 minutes x 1000 Btu/cu. ft. x 20

EXAMPLE #2:

For 1050 Btu/cu. ft. gas, this becomes:

Btuh Input = cu. ft. metered in 3 minutes x 1050 Btu/cu. ft. x 20

4.The higher heating value of gas varies substantially for different localities. Consult with Slant/Fin’s Technical Ser- vice Department for reorificing procedures if any of the following apply:

a.Boiler (burner) is over firing. CAUTION! National Fuel Gas Code (ANSI Z223. -latest edition) does NOT per- mit firing at a higher input rate than the input rate indi- cated on the boiler rating plate in order to avoid haz- ardous conditions such as explosion or carbon monox- ide poisoning.

b.Poor higher heating value of gas is causing the actual input to be substantially lower than the rating plate indication.

 

Gas Rate Table

 

 

Boiler rated input in

Cubic Feet Gas Consumption

cu. ft./hr. of 1000 Btu/cu. ft.

1000 Btu/cu. ft. gas, in

Natural Gas

3 minutes, at rated input

 

 

60

3.00

90

4.50

120

6.00

150

7.50

180

9.00

The gas metered in 3 minutes to obtain rated input for each boiler model, using 1000 Btu/cu. ft. gas, is tabu- lated in gas rate table.

INTEGRATED BOILER CONTROL

The integrated boiler control monitors the status of the room thermostat, high limit control (Aquastat), pressure switch and the flame sensor. It controls the operation of circulator, induc- er motor, gas valve and spark for pilot ignition. The boiler con- trol also determines the sequence of operation and timing for pre and post purge periods, trail for ignition and lockout.

The control indicator lights (LED’s) provide information of boil- er operation when lights are steady on or diagnostic informa- tion when they are flashing in order to help to determine the cause of boiler failure.

A. NORMAL OPERATION - STATUS OF INDICATOR LIGHTS (LED’S)

O = LED off

= LED steady on

DESCRIPTION OF OPERATION

POWER

TSTAT/CIRC

 

LED

LED

 

 

Standby-Boiler waits for call for

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

heat

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat calls for heat

Circulator on

Boiler water temperature below high limit setting

Inducer on

Pressure switch contacts closed 30 seconds pre-purge period Trial for ignition

Gas valve open

Pilot flame and main burners on

Boiler heating period

Thermostat call for heat ends

 

 

O

Circulator off

 

 

 

 

15 seconds post purge period.

 

 

 

 

 

 

 

 

Burners off.

 

 

 

LIMIT

PRESS

 

SWITCH

FLAME

LED

LED

LED

O

O

O

O

O

O

 

O

O

 

 

O

O

Image 22
Contents Table of Contents Victory VsphVictory Vsph Models Ratings and DimensionsBoiler Input No. Model Btuh Sections Base Assembly Location and Identification of PartsLiquefied Petroleum L.P. Propane GAS-FIRED Boiler Location SafetyNatural GAS-FIRED Boiler Location Boiler FoundationVenting Application NON-DIRECT Vent InstallationDirect Vent Installation Boiler Room AIR Supply and VentilationAIR Intake Pipe Material Flue and AIR Intake Restrictions000 Ft 000 7,500 Ft 500 10,000 Ft Sidewall Venting NON-DIRECT Vent Venting InstallationVENT/AIR Intake Termination Installation Vent Termination Location and ClearancesVictory Vsph Models NON Direct VENT, Sidewall Venting Non-direct vent, side wall ventingAL 29-4C is a Registered Trademark of Allegheny Ludlum Corp Victory Vsph Models Victory Vsph Models Direct VENT, Sidewall Venting Direct Vent Venting and AIR Intake Through a Roof Vent/Air Intake TerminationVictory Vsph Models Direct VENT, Venting and AIR Intake Through a RoofVenting and AIR Intake System Regular Inspection Electrical WiringPower Supply GAS PipingSchematic wiring diagram Multizoning of Vsph Boiler Multi Zoning Thermostat ConnectionsWater Piping Operating Instructions Safety Information Vsph Boiler Sequence of Operation Limit Press Switch Flame LED Normal Operation Status of Indicator Lights LED’SDescription of Operation Power TSTAT/CIRC LED Integrated Boiler ControlLED’s Flashing Diagnostic Flash CodesIndication Remedy Cleaning Care and MaintenanceGeneral Maintenance II. Inspection During Heating SeasonGeneral Troubleshooting Guide For Service Personnel Burners Fail to OPERATE- no Heat CauseNot Enough Heat Cause Burner will not Shut OFF CauseBurner Short Cycles Cause Remedy If Replacement Parts are NeededFumes and GAS Odors Cause Remedy SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

VSPH-180, VSPH-60 specifications

Slant/Fin is a renowned name in the heating industry, renowned for its innovation, quality, and efficiency. Among its popular offerings are the VSPH-180 and VSPH-60, two highly efficient gas-fired residential boilers designed to provide reliable heating for homes.

The VSPH-180 is a high-efficiency residential boiler that delivers exceptional heating performance while being mindful of energy consumption. It operates at an impressive AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, meaning it uses 95% of the fuel burned for heating, resulting in lower energy bills and reduced environmental impact. The VSPH-180 features a durable stainless steel heat exchanger that not only contributes to its efficiency but also prolongs the boiler's lifespan.

On the other hand, the VSPH-60 is a slightly smaller but equally efficient model that is perfect for apartments or smaller homes. It also boasts a remarkable AFUE rating of up to 95%, ensuring cost-effective heating solutions. The compact design of the VSPH-60 allows for easy installation in various locations, making it a versatile choice for homeowners seeking space-saving options without compromising on performance.

One of the standout technologies in both models is the modulating gas valve, which adjusts the burner’s output to match the heating demand. This feature enhances energy efficiency by preventing the boiler from working harder than necessary, ensuring consistent temperatures and reducing wear on the unit. Furthermore, both models are equipped with a built-in electronic ignition system, eliminating the need for a pilot light and adding convenience for homeowners.

The VSPH series is designed with maintenance ease in mind. It features a user-friendly control panel that provides easy access to critical information, allowing for straightforward diagnostics and service. Regular maintenance can be performed with minimal disruption, enabling owners to keep their systems running optimally throughout the heating season.

In conclusion, the Slant/Fin VSPH-180 and VSPH-60 represent excellence in residential heating technology. With high AFUE ratings, durable construction, and advanced features, both boilers provide efficient and reliable heating solutions, ensuring comfort and energy savings for homeowners.