Slant/Fin VSPH-180 Venting and AIR Intake System Regular Inspection, GAS Piping, Power Supply

Page 15

VICTORY VSPH Models

15

 

 

 

VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION

A.Inspect the system regularly for condensation, corrosion and/or physical damage. A qualified professional should ser- vice the boiler annually and include such an inspection at that time. The homeowner should look over the system monthly for damage, water stains, any signs of rust, other corrosions or separation of the vent and air intake piping (if direct-vent).

B.Should an inspection turn up signs of condensation, corrosion or damage, the boiler should be shut down immediately and the condition should be corrected by a qualified professional.

C.All Victory VSPH boilers are equipped with a built-in conden- sation drain and trap. The trap loop must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. Periodic inspection should be made of this assembly for deterioration of the tub- ing and to insure that the trap is not plugged. If it is plugged or appears to have excessive sediment in it, it should be removed from the drain assembly, straightened out to clear the obstruction, reformed, filled with water and reinstalled as before.

GAS PIPING

A.Local installation codes apply. The pipe joint compound used on threads must be resistant to the action of liquefied petroleum gases.

B.The gas supply line to the boiler should run directly from the meter for natural gas or from the fuel tank for L.P. propane gas. See page 2 for location of union and manual main shut-off valve that may be specified locally.

Selecting pipe size for natural gas:

1.Measure or estimate the length of piping from the meter to the installation site.

2.Consult gas supplier for heating value of gas (Btu/cu. ft.).

3.Divide boiler rated input by heating value to find gas flow in piping (cu. ft. per hour).

4.Use table below to select proper pipe size.

EXAMPLE: Boiler model VSPH-150 is to be installed. Distance from gas meter to the boilers is 30ft. Heating value of natural gas is 1020 Btu/cu. Ft. Select proper pipe size.

Gas flow = 150,000 Btu/hour = 147 cu. ft. per hour 1020 Btu/cu. ft.

At 30 ft. length of pipe, match required capacity from table on this page (choose higher capacity, in this case is 152 cu. ft. per hour). Required pipe size is 34".

Improper gas pipe sizing will result in pilot flame outages, insuf- ficient heat and other installation difficulties. For more informa- tion and also if other appliances are to be attached to the pip- ing system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.

C.The boiler and its gas connection must be leak tested before placing the boiler in operation. Use liquid soap solu- tion for all gas leak testing. DO NOT use open flame. This boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure test- ing of that system at test pressures in excess of 12 PSIG. This boiler must be isolated from the gas supply piping sys- tem by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 12 PSIG.

D.All gas piping used should be inspected thoroughly for cleanliness before makeup. A sediment trap must be provid- ed, as illustrated on page 2.

E.The minimum and maximum gas supply pressure (at the inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.

Length

 

Gas Flow In piping -- cu. ft. per hr.

 

 

 

Iron Pipe Size (IPS) — inches

 

of pipe

 

 

 

 

 

 

 

 

 

 

in Feet

1/2

 

3 4

1

1 4

 

1

 

 

 

/

1 /

 

1 /2

10

132

 

278

520

1050

 

1600

20

92

 

190

350

730

 

1100

30

73

 

152

285

590

 

890

40

63

 

130

245

500

 

760

50

56

 

115

215

440

 

670

60

50

 

105

195

400

 

610

70

46

 

96

180

370

 

560

80

43

 

90

170

350

 

530

90

40

 

84

160

320

 

490

100

38

 

79

150

305

 

460

At pressure drop of 0.3 in. water, specific gravity = 0.6.

ELECTRICAL WIRING

DANGER: Before wiring always turn off electric power supply otherwise, shock or death can result.

1.Power Supply

A separately fused circuit is recommended. Use standard 15 Amp. fuse or breaker and 14 gage conductors in BX cable or conduit.

Provide disconnect means and overload protection as required. See boiler wiring diagram (Figure 13a) boiler con- trol (Figure13b) and ladder diagram (Figure 13c).

Boiler must be electrically grounded in accordance with the requirements of the authority having jurisdiction, or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70-latest edition.

Image 15
Contents Victory Vsph Table of ContentsRatings and Dimensions Victory Vsph ModelsBoiler Input No. Model Btuh Sections Location and Identification of Parts Base AssemblyBoiler Foundation SafetyNatural GAS-FIRED Boiler Location Liquefied Petroleum L.P. Propane GAS-FIRED Boiler LocationBoiler Room AIR Supply and Ventilation NON-DIRECT Vent InstallationDirect Vent Installation Venting ApplicationFlue and AIR Intake Restrictions AIR Intake Pipe Material000 Ft 000 7,500 Ft 500 10,000 Ft Vent Termination Location and Clearances Venting InstallationVENT/AIR Intake Termination Installation Sidewall Venting NON-DIRECT VentNon-direct vent, side wall venting Victory Vsph Models NON Direct VENT, Sidewall VentingAL 29-4C is a Registered Trademark of Allegheny Ludlum Corp Victory Vsph Models Victory Vsph Models Direct VENT, Sidewall Venting Vent/Air Intake Termination Direct Vent Venting and AIR Intake Through a RoofDirect VENT, Venting and AIR Intake Through a Roof Victory Vsph ModelsGAS Piping Electrical WiringPower Supply Venting and AIR Intake System Regular InspectionSchematic wiring diagram Multizoning of Vsph Boiler Thermostat Connections Multi ZoningWater Piping Operating Instructions Safety Information Vsph Boiler Sequence of Operation Integrated Boiler Control Normal Operation Status of Indicator Lights LED’SDescription of Operation Power TSTAT/CIRC LED Limit Press Switch Flame LEDDiagnostic Flash Codes LED’s FlashingIndication Remedy II. Inspection During Heating Season Care and MaintenanceGeneral Maintenance CleaningBurners Fail to OPERATE- no Heat Cause General Troubleshooting Guide For Service PersonnelBurner will not Shut OFF Cause Not Enough Heat CauseIf Replacement Parts are Needed Burner Short Cycles Cause RemedyFumes and GAS Odors Cause Remedy SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

VSPH-180, VSPH-60 specifications

Slant/Fin is a renowned name in the heating industry, renowned for its innovation, quality, and efficiency. Among its popular offerings are the VSPH-180 and VSPH-60, two highly efficient gas-fired residential boilers designed to provide reliable heating for homes.

The VSPH-180 is a high-efficiency residential boiler that delivers exceptional heating performance while being mindful of energy consumption. It operates at an impressive AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, meaning it uses 95% of the fuel burned for heating, resulting in lower energy bills and reduced environmental impact. The VSPH-180 features a durable stainless steel heat exchanger that not only contributes to its efficiency but also prolongs the boiler's lifespan.

On the other hand, the VSPH-60 is a slightly smaller but equally efficient model that is perfect for apartments or smaller homes. It also boasts a remarkable AFUE rating of up to 95%, ensuring cost-effective heating solutions. The compact design of the VSPH-60 allows for easy installation in various locations, making it a versatile choice for homeowners seeking space-saving options without compromising on performance.

One of the standout technologies in both models is the modulating gas valve, which adjusts the burner’s output to match the heating demand. This feature enhances energy efficiency by preventing the boiler from working harder than necessary, ensuring consistent temperatures and reducing wear on the unit. Furthermore, both models are equipped with a built-in electronic ignition system, eliminating the need for a pilot light and adding convenience for homeowners.

The VSPH series is designed with maintenance ease in mind. It features a user-friendly control panel that provides easy access to critical information, allowing for straightforward diagnostics and service. Regular maintenance can be performed with minimal disruption, enabling owners to keep their systems running optimally throughout the heating season.

In conclusion, the Slant/Fin VSPH-180 and VSPH-60 represent excellence in residential heating technology. With high AFUE ratings, durable construction, and advanced features, both boilers provide efficient and reliable heating solutions, ensuring comfort and energy savings for homeowners.