11.0Install Termination
11.1Slide the termination body onto the cable and remove core. Pull while unwinding,
with the loose end (Figure 15). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 15).
NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE.
| |
Vinyl Tape Marker |
|
NOTE: The material being removed at this step is mixed polymers | |
and can be recycled with | waste. |
Figure 15
11.2 Connect ground braid to system ground according to standard practice.
Correct Installation of Termination on Wire Shielded Cable |
| |
Vi nyl Tape |
|
|
Marker | Ridge at End of Cable |
|
|
| |
Ridge at End | Insulation Shield |
|
|
| |
of |
|
|
Cable | Envioronmental Top | |
Stress Controlling Compound | Insulation | Seal |
Conductor |
| |
| ||
|
| |
|
| Relief Tube |