Instructions For Tape Shielded Cable
2.0Prepare Cable
2.1Check to be sure cable size fits within kit size range as shown in Table 1 (page 2).
2.2Prepare cable using dimensions shown in Figure 1. Be sure to allow for depth of terminal lug. Refer to
Table 2 for
NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:
Aluminum Connector | 2 - 350 | 400 - 650 |
Growth Allowance | 1/4” (6 mm) | 1/2" (13 mm) |
NOTE: It is imperative to remove all remnants of the
Kit Number | Insulation 0.D. | 15 kV | 25/28 kV | 35 kV |
| |
AWG / kcmil | AWG / kcmil | AWG / kcmil | Cutback | |||
|
| |||||
|
|
|
|
|
| |
| 0.83" - 1.21" | 4/0 - 300 | 2 - 2/0 | 13.5" | ||
(21,1 - 30,7 mm) | (120 - 150 mm2) | (70 - 95 mm2) | (35 - 70 mm2) | (342,9 mm) | ||
|
|
|
|
| ||
0.98" - 1.53" | 350 - 500 | 4/0 - 250 | 3/0 - 4/0 | 13.0" | ||
| ||||||
| (24,9 - 38,9 mm) | (185 - 240 mm2) | (120 - 150 mm2) | (95 - 120 mm2) | (330,2 mm) | |
|
|
|
|
|
|
Table 2
| Jacket Removal Length |
Depth Of Terminal Lug + Growth Allowance | |
3” (76 mm) | |
1 1/ 2” |
|
(38 mm) |
|
| |
Tape Shield |
|
Cable Jacket |
|
Figure 1
3 |