3M 7684-S-8 manual Instructions For Tape Shielded Cable, Prepare Cable

Page 3

Instructions For Tape Shielded Cable

2.0Prepare Cable

2.1Check to be sure cable size fits within kit size range as shown in Table 1 (page 2).

2.2Prepare cable using dimensions shown in Figure 1. Be sure to allow for depth of terminal lug. Refer to

Table 2 for semi-con cutback dimension. If necessary to prevent tape shield from unrolling, hold down edge with a single wrap of 3M™ EMI Copper Foil Shielding Tape 1181.

NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:

Aluminum Connector

2 - 350

400 - 650

Growth Allowance

1/4” (6 mm)

1/2" (13 mm)

NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.

Kit Number

Insulation 0.D.

15 kV

25/28 kV

35 kV

Semi-con

AWG / kcmil

AWG / kcmil

AWG / kcmil

Cutback

 

 

 

 

 

 

 

 

 

0.83" - 1.21"

4/0 - 300

2/0-3/0

2 - 2/0

13.5"

7684-S-8

(21,1 - 30,7 mm)

(120 - 150 mm2)

(70 - 95 mm2)

(35 - 70 mm2)

(342,9 mm)

 

 

 

 

 

0.98" - 1.53"

350 - 500

4/0 - 250

3/0 - 4/0

13.0"

 

 

(24,9 - 38,9 mm)

(185 - 240 mm2)

(120 - 150 mm2)

(95 - 120 mm2)

(330,2 mm)

 

 

 

 

 

 

Table 2

 

Jacket Removal Length

Depth Of Terminal Lug + Growth Allowance

3” (76 mm)

Semi-Con Cutback

1 1/ 2”

 

(38 mm)

 

 

Semi-Con

Tape Shield

 

Cable Jacket

 

Figure 1

78-8117-0985-2 Rev C

3

Image 3
Contents 7684-S-8 Instructions With High-K Stress ReliefKit Contents Prepare Cable Instructions For Tape Shielded CableInstall Ground Braid Special Note for Cloth or Paper SEMI-CON Insulation Shield Do not Remove Core AT this Time Install Lug or ConnectorVinyl Tape Marker Install TerminationSure to allow for depth of terminal lug Instructions for Wire Shielded Cable6 mm Constant Force Spring Trim Shield Wires This Time Counter-Clockwise Allow for depth of terminal lug Instructions for UniShield Shielded CableRemove semi-conductive jacket to dimension shown in Figure Shield Wire ND Scotch Mastic Strip Install Lug or Connector Vinyl Tape Marker Ridge at End of Cable Thru 30045 One hole Tooling IndexThru 40079 One hole Thru 40178 Two hole Conductor Size AWG & kcmil Stranded Important Notice