3M 7684-S-8 manual Instructions for Wire Shielded Cable, Sure to allow for depth of terminal lug

Page 8

Instructions for Wire Shielded Cable

7.0Prepare Cable

7.1Check to be sure cable size fits within kit size range as shown in Table 1 (page 2).

7.2Prepare cable using dimensions shown in Figure 8 and 9. Refer to Table 3 for semi-con cutback dimension. Be

sure to allow for depth of terminal lug.

NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:

Aluminum Connector

2 - 350

400 - 650

Growth Allowance

1/4” (6 mm)

1/2" (13 mm)

 

 

 

NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.

Kit Number

Insulation 0.D.

15 kV

25/28 kV

35 kV

Semi-con

AWG / kcmil

AWG / kcmil

AWG / kcmil

Cutback

 

 

 

 

 

 

 

 

 

0.83" - 1.21"

4/0 - 300

2/0-3/0

2 - 2/0

13.5"

7684-S-8

(21,1 - 30,7 mm)

(120 - 150 mm2)

(70 - 95 mm2)

(35 - 70 mm2)

(342,9 mm)

 

 

 

 

 

0.98" - 1.53"

350 - 500

4/0 - 250

3/0 - 4/0

13.0"

 

 

(24,9 - 38,9 mm)

(185 - 240 mm2)

(120 - 150 mm2)

(95 - 120 mm2)

(330,2 mm)

 

 

 

 

 

 

Table 3

 

 

Jacket Removal Length

 

 

Depth Of Terminal Lug + Growth Allowance

3

(76 mm)

Semi-Con Cutback

 

 

Semi-Con

 

Shield Wires

CableJacket

Figure 8

7.3Bend leading 1 1/2" (38 mm) of exposed shield wires back upon themselves to jacket edge (Figure 9).

 

 

3

(76 mm)

1 1/2

(38 mm)

 

 

 

 

Semi-Con

 

Cable Jacket

Shield Wires

Figure 9

8

78-8117-0985-2 Rev C

Image 8
Contents With High-K Stress Relief 7684-S-8 InstructionsKit Contents Instructions For Tape Shielded Cable Prepare CableInstall Ground Braid Special Note for Cloth or Paper SEMI-CON Insulation Shield Install Lug or Connector Do not Remove Core AT this TimeInstall Termination Vinyl Tape MarkerInstructions for Wire Shielded Cable Sure to allow for depth of terminal lug6 mm Constant Force Spring Trim Shield Wires This Time Counter-Clockwise Instructions for UniShield Shielded Cable Allow for depth of terminal lugRemove semi-conductive jacket to dimension shown in Figure Shield Wire ND Scotch Mastic Strip Install Lug or Connector Vinyl Tape Marker Ridge at End of Cable Tooling Index Thru 30045 One holeThru 40079 One hole Thru 40178 Two hole Conductor Size AWG & kcmil Stranded Important Notice