Instructions for Wire Shielded Cable
7.0Prepare Cable
7.1Check to be sure cable size fits within kit size range as shown in Table 1 (page 2).
7.2Prepare cable using dimensions shown in Figure 8 and 9. Refer to Table 3 for
sure to allow for depth of terminal lug.
NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:
Aluminum Connector | 2 - 350 | 400 - 650 |
Growth Allowance | 1/4” (6 mm) | 1/2" (13 mm) |
|
|
|
NOTE: It is imperative to remove all remnants of the
Kit Number | Insulation 0.D. | 15 kV | 25/28 kV | 35 kV | ||
AWG / kcmil | AWG / kcmil | AWG / kcmil | Cutback | |||
|
| |||||
|
|
|
|
|
| |
| 0.83" - 1.21" | 4/0 - 300 | 2 - 2/0 | 13.5" | ||
(21,1 - 30,7 mm) | (120 - 150 mm2) | (70 - 95 mm2) | (35 - 70 mm2) | (342,9 mm) | ||
|
|
|
|
| ||
0.98" - 1.53" | 350 - 500 | 4/0 - 250 | 3/0 - 4/0 | 13.0" | ||
| ||||||
| (24,9 - 38,9 mm) | (185 - 240 mm2) | (120 - 150 mm2) | (95 - 120 mm2) | (330,2 mm) | |
|
|
|
|
|
|
Table 3
|
| Jacket Removal Length |
|
| Depth Of Terminal Lug + Growth Allowance |
3 | (76 mm) | |
|
| |
| Shield Wires | |
CableJacket |
Figure 8
7.3Bend leading 1 1/2" (38 mm) of exposed shield wires back upon themselves to jacket edge (Figure 9).
|
| 3 | (76 mm) |
1 1/2 | (38 mm) |
|
|
|
| ||
| Cable Jacket | Shield Wires |
Figure 9