3M 7684-S-8 manual Vinyl Tape Marker Ridge at End of Cable

Page 18

16.0Install Termination

16.1Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting

with the loose end (Figure 24). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 24).

NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING THE CORE.

 

Counter-Clockwise

Vinyl Tape Marker

NOTE: The material being removed at this step is mixed polymers

 

and can be recycled with

waste.

Figure 24

16.2 Connect ground braid to system ground according to standard practice

Correct Installation of Termination on UniShield® Shielded Cable

Vinyl Tape

 

 

Marker

Ridge at End of Cable

 

 

 

Ridge at End

Insulation Shield (Semi-Con)

 

 

 

of High-K Tube

 

 

Semi-Con Insulation Shield

Cable

Environmental

Stress Controlling Compound

Insulation

Top Seal

 

Conductor

High-K Stress

 

 

 

 

Relief Tube

 

18

78-8117-0985-2 Rev C

Image 18
Contents With High-K Stress Relief 7684-S-8 InstructionsKit Contents Instructions For Tape Shielded Cable Prepare CableInstall Ground Braid Special Note for Cloth or Paper SEMI-CON Insulation Shield Install Lug or Connector Do not Remove Core AT this TimeInstall Termination Vinyl Tape MarkerInstructions for Wire Shielded Cable Sure to allow for depth of terminal lug6 mm Constant Force Spring Trim Shield Wires This Time Counter-Clockwise Instructions for UniShield Shielded Cable Allow for depth of terminal lugRemove semi-conductive jacket to dimension shown in Figure Shield Wire ND Scotch Mastic Strip Install Lug or Connector Vinyl Tape Marker Ridge at End of Cable Tooling Index Thru 30045 One holeThru 40079 One hole Thru 40178 Two hole Conductor Size AWG & kcmil Stranded Important Notice