3M 7684-S-8 manual Install Ground Braid

Page 4

3.0Install Ground Braid

3.1Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a single

wrap of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 2). Cut off excess.

1/4” (6 mm)

 

 

Semi-Con

 

Tape Shield

1ST

Scotch® Mastic Strip 2230

Cable Jacket

 

Figure 2

3.2Position preformed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASE NOTE: The ground braid needs to make full contact with the metallic shield. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 3). Secure ground braid to cable jacket 4 l/2" (114 mm) from cable semi-con edge using vinyl tape (Figure 3).

NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination.

4 1/2

(1 14

mm)

 

 

Semi-Con Edge

 

 

Tape Shield

 

 

Ground Braid

 

 

Cable Jacket Edge

 

Solder Block

 

 

1 ST Scotch® Mastic Strip 2230

Vinyl Tape Marker

Figure 3

4

78-8117-0985-2 Rev C

Image 4
Contents With High-K Stress Relief 7684-S-8 InstructionsKit Contents Instructions For Tape Shielded Cable Prepare CableInstall Ground Braid Special Note for Cloth or Paper SEMI-CON Insulation Shield Install Lug or Connector Do not Remove Core AT this TimeInstall Termination Vinyl Tape MarkerInstructions for Wire Shielded Cable Sure to allow for depth of terminal lug6 mm Constant Force Spring Trim Shield Wires This Time Counter-Clockwise Instructions for UniShield Shielded Cable Allow for depth of terminal lugRemove semi-conductive jacket to dimension shown in Figure Shield Wire ND Scotch Mastic Strip Install Lug or Connector Vinyl Tape Marker Ridge at End of Cable Tooling Index Thru 30045 One holeThru 40079 One hole Thru 40178 Two hole Conductor Size AWG & kcmil Stranded Important Notice