3MCold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

With High-K Stress Relief

For Tape Shield, Wire Shield and UniShield® Cable

7622-T-110, 7623-T-110, 7624-T-110, 7625-T-110,

7626-T-110

Instructions

IEEE Std. No. 48 Class 1 Termination 15 kV Class

110 kV BIL

FCAUTION

Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product.

September 2014

3

78-8113-5099-6 Rev E

Image 1
Contents Ieee Std. No Class 1 Termination 15 kV Class 7626-T-110 InstructionsKit Selection Table Kit ContentsInstructions for Tape Shielded Cable Install Ground BraidPrepare Cable Aluminum Lug 400 750-1000 1250Rev E Special Note for Cloth or Paper SEMI-CON Insulation Shield Install Lug or ConnectorCorrect Installation of Termination on Tape Shielded Cable Install TerminationTerminal LUG Instructions for Wire Shielded Cable6 mm Semi-Con 1st Scotch Mastic Strip 2230 Cable Jacket Cable Do not Allow Solvent to Touch SEMI-CON Insulation Shield Connector/LugInstructions for UniShield Shielded Cable Correct Installation of Termination on Wire Shielded CableRemove semi-conductive jacket to dimension shown in Figure 1st Scotch Mastic Strip Constant Force Spring Shield Wires Polymers and can be recycled Environmental Top Thru 30045 One hole Tooling IndexCrimping Tool-Die Sets Minimum Number Of Crimps Thru 40079 One hole Thru 40178 Two holeConductor Size AWG & kcmil Stranded 3M Connector Number ManufacturerRecommended Crimping Tools Mech. Tool Die Minimum No CrimpsImportant Notice Warranty Limited Remedy Limited Liability