3M 7622-T-110 Install Termination, Correct Installation of Termination on Tape Shielded Cable

Page 6

6.0Install Termination

6.1Slide the termination body onto the cable and remove core. Make sure the termination body (not the core) is butted

up to the edge of the vinyl tape marker previously applied (Figure 7). Pull the core while unwinding, counter- clockwise, starting with the loose end (Figure 7). Be sure to alternate the pulling and unwinding actions (pull- unwind-pull-unwind-etc.) to help prevent the core material from binding up as the core is being removed.

NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. Do not push or pull on the termination assembly while unwinding the core.

Counterclockwise

Vinyl Tape Marker

NOTE: The material being removed at this step is mixed polymers

 

and can be recycled.

Figure 7

6.2Connect ground braid to system ground according to standard practice.

Correct Installation of Termination on Tape Shielded Cable

 

Vinyl Tape

 

 

Marker

Ridge at End of Cable

 

 

 

 

Insulation Shield (Semi-Con)

 

Ridge at End

 

 

of High-K Tube

 

 

Semi-Con Insulation Shield

Cable Insulation

Environmental Top

Stress Controlling Compound

Conductor

Seal

 

 

 

High-K Stress

 

 

Relief Tube

6

78-8113-5099-6 Rev E

Image 6
Contents 7626-T-110 Instructions Ieee Std. No Class 1 Termination 15 kV ClassKit Contents Kit Selection TablePrepare Cable Install Ground BraidInstructions for Tape Shielded Cable Aluminum Lug 400 750-1000 1250Rev E Install Lug or Connector Special Note for Cloth or Paper SEMI-CON Insulation ShieldInstall Termination Correct Installation of Termination on Tape Shielded CableInstructions for Wire Shielded Cable Terminal LUG6 mm Semi-Con 1st Scotch Mastic Strip 2230 Cable Jacket Cable Connector/Lug Do not Allow Solvent to Touch SEMI-CON Insulation ShieldCorrect Installation of Termination on Wire Shielded Cable Instructions for UniShield Shielded CableRemove semi-conductive jacket to dimension shown in Figure 1st Scotch Mastic Strip Constant Force Spring Shield Wires Polymers and can be recycled Environmental Top Tooling Index Thru 30045 One holeThru 40079 One hole Thru 40178 Two hole Crimping Tool-Die Sets Minimum Number Of CrimpsRecommended Crimping Tools Mech. Tool 3M Connector Number ManufacturerConductor Size AWG & kcmil Stranded Die Minimum No CrimpsWarranty Limited Remedy Limited Liability Important Notice