3M 7624-T-110, 7626-T-110, 7622-T-110, 7623-T-110, 7625-T-110 manual Kit Contents, Kit Selection Table

Page 2

1.0 Kit Contents

3 High–K, Tracking Resistant, Silicone Rubber Terminations

3 Pre-formed Ground Braids

3 Constant Force Springs

3 3MEMI Copper Foil Shielding Tape 1181 Strips, 1/2" x 10"

6 Strips Scotch® Mastic Strip 2230 (black with white release liners, bagged) 1 3MCable Cleaning Preparation Kit CC-2

1 Instruction Sheet

Note: Do not use knives to open plastic bags.

Kit Selection Table

NOTE: Final Determination Factor is cable insulation diameter.

 

Primary Insulation

 

 

Conductor Size Range (AWG & kcmil)

 

 

 

 

 

 

 

 

Kit Number

O.D. Range

Jacket O.D, Range

5 kV

8 kV

15 kV

7622–T–110

0.64" – 1.08"

0.97" – 1.48"

4/0 – 400

3/0 – 300

2 – 2/0

(16,3 – 27,4 mm)

(24,6 – 37,7 mm)

 

 

(35 –

70 mm2)

7623–T–110

0.72" – 1.29"

1.04" – 1.60"

300

– 500

250

– 500

2/0 – 300

(18,3 – 32,8 mm)

(26,4 – 40,6 mm)

 

 

(70 – 150 mm2)

7624–T–110

0.83" – 1.53"

1.12" – 1.87"

500

– 750

350

– 700

4/0 – 500

(21,1 – 38,9 mm)

(28,4 – 47,5 mm)

 

 

(120 –

240 mm2)

7625–T–110

1.05" – 1.80"

1.39" – 2.40"

700 – 1500

600 – 1250

500

– 1000

(26,7 – 45,7 mm)

(35,2 – 61,0 mm)

 

 

(240 –

500 mm2)

7626–T–110

1.53" – 2.32"

1.84" – 2.80"

1750

– 2000

1500

– 2000

1250 – 2000

(38,9 – 58,9 mm)

(46,7 – 71,1 mm)

 

 

(625 – 1000 mm2)

Table 1

2

78-8113-5099-6 Rev E

Image 2
Contents 7626-T-110 Instructions Ieee Std. No Class 1 Termination 15 kV ClassKit Contents Kit Selection TablePrepare Cable Install Ground BraidInstructions for Tape Shielded Cable Aluminum Lug 400 750-1000 1250Rev E Install Lug or Connector Special Note for Cloth or Paper SEMI-CON Insulation ShieldInstall Termination Correct Installation of Termination on Tape Shielded CableInstructions for Wire Shielded Cable Terminal LUG6 mm Semi-Con 1st Scotch Mastic Strip 2230 Cable Jacket Cable Connector/Lug Do not Allow Solvent to Touch SEMI-CON Insulation ShieldCorrect Installation of Termination on Wire Shielded Cable Instructions for UniShield Shielded CableRemove semi-conductive jacket to dimension shown in Figure 1st Scotch Mastic Strip Constant Force Spring Shield Wires Polymers and can be recycled Environmental Top Tooling Index Thru 30045 One holeThru 40079 One hole Thru 40178 Two hole Crimping Tool-Die Sets Minimum Number Of CrimpsRecommended Crimping Tools Mech. Tool 3M Connector Number ManufacturerConductor Size AWG & kcmil Stranded Die Minimum No CrimpsWarranty Limited Remedy Limited Liability Important Notice