NOTE: Refer to pages 17-19 for 3M connector and lug crimping information.

NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Insert conductor into lug or connector and then remove conductor. This will transfer some of the antioxidant compound onto the conductor. Wire brush the anti-oxidant paste into the strands. Immediately insert conductor into lug or connector barrel as far as it will go.

NOTE: Die/crimper head rotation between consecutive crimps is RECOMMENDED.

14.2Position connector or lug and crimp according to manufacturer's directions. Remove excess oxide inhibitor and sharp crimp flashings following crimping.

15.0Clean Cable Insulation and Lug or Connector Barrel Using Standard Practice

15.1Wipe the cable insulation with one of the solvent saturated pads from the 3MCable Cleaning Preparation Kit CC-2.

DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD!

15.2If abrasive must be used:

a.Use on insulation only. DO NOT USE ABRASIVE ON SEMI-CON INSULATION SHIELD!

b.Use only aluminum oxide abrasive; grit 120 or finer, included in the 3M Cable Cleaning Preparation Kit CC-2.

c.Be careful not to reduce the cable insulation diameter below that allowed by the kit.

16.0Install Termination

16.1Slide the termination body onto the cable and remove core. Make sure the termination body (not the core) is butted

up to the edge of the vinyl tape marker previously applied (Figure 24). Pull the core while unwinding, counter- clockwise, starting with the loose end (Figure 24). Be sure to alternate the pulling and unwinding actions (pull- unwind-pull-unwind-etc.) to help prevent the core material from binding up as the core is being removed.

NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue supporting the assembly. Do not push or pull on the termination assembly while unwinding the core.

Counterclockwise

Vinyl Tape Marker

NOTE: The material being removed at this step is mixed

 

polymers and can be recycled.

Figure 24

16.2 Connect ground braid to system ground according to standard practice.

78-8113-5099-6 Rev E

15

Image 15
Contents Ieee Std. No Class 1 Termination 15 kV Class 7626-T-110 InstructionsKit Selection Table Kit ContentsAluminum Lug 400 750-1000 1250 Install Ground BraidInstructions for Tape Shielded Cable Prepare CableRev E Special Note for Cloth or Paper SEMI-CON Insulation Shield Install Lug or ConnectorCorrect Installation of Termination on Tape Shielded Cable Install TerminationTerminal LUG Instructions for Wire Shielded Cable6 mm Semi-Con 1st Scotch Mastic Strip 2230 Cable Jacket Cable Do not Allow Solvent to Touch SEMI-CON Insulation Shield Connector/LugInstructions for UniShield Shielded Cable Correct Installation of Termination on Wire Shielded CableRemove semi-conductive jacket to dimension shown in Figure 1st Scotch Mastic Strip Constant Force Spring Shield Wires Polymers and can be recycled Environmental Top Thru 30045 One hole Tooling IndexCrimping Tool-Die Sets Minimum Number Of Crimps Thru 40079 One hole Thru 40178 Two holeDie Minimum No Crimps 3M Connector Number ManufacturerConductor Size AWG & kcmil Stranded Recommended Crimping Tools Mech. ToolImportant Notice Warranty Limited Remedy Limited Liability