3M 7625-T-110, 7626-T-110, 7622-T-110, 7624-T-110, 7623-T-110 Constant Force Spring Shield Wires

Page 14

Constant Force Spring Shield Wires

Ground Braid

1st Scotch® Mastic Strip 2230 Solder Block

2nd Scotch® Mastic Strip 2230

Trim

Cable

Wire

Shield

Ground Braid Leg

Figure 21

13.5Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 22).

NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.

1-1/2" (38 mm)

Semi-Con

Shield Wires

Constant Force Spring

Two Half-Lapped Layers of Electrical Grade Vinyl Tape

Scotch® Mastic Strip 2230

Vinyl Tape Marker

Figure 22

14.0 Install Lug or Connector

Important Packaging Notice

In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination. This shipping core can be recycled with other polypropylene waste.

14.1Check to insure 3MCold Shrink QT -III Silicone Rubber Termination fits over the selected lug or connector. If lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME.

Clearance

Connector/Lug

Figure 23

14

78-8113-5099-6 Rev E

Image 14
Contents 7626-T-110 Instructions Ieee Std. No Class 1 Termination 15 kV ClassKit Contents Kit Selection TablePrepare Cable Install Ground BraidInstructions for Tape Shielded Cable Aluminum Lug 400 750-1000 1250Rev E Install Lug or Connector Special Note for Cloth or Paper SEMI-CON Insulation ShieldInstall Termination Correct Installation of Termination on Tape Shielded CableInstructions for Wire Shielded Cable Terminal LUG6 mm Semi-Con 1st Scotch Mastic Strip 2230 Cable Jacket Cable Connector/Lug Do not Allow Solvent to Touch SEMI-CON Insulation ShieldCorrect Installation of Termination on Wire Shielded Cable Instructions for UniShield Shielded CableRemove semi-conductive jacket to dimension shown in Figure 1st Scotch Mastic Strip Constant Force Spring Shield Wires Polymers and can be recycled Environmental Top Tooling Index Thru 30045 One holeThru 40079 One hole Thru 40178 Two hole Crimping Tool-Die Sets Minimum Number Of CrimpsRecommended Crimping Tools Mech. Tool 3M Connector Number ManufacturerConductor Size AWG & kcmil Stranded Die Minimum No CrimpsWarranty Limited Remedy Limited Liability Important Notice