Constant Force Spring Shield Wires
Ground Braid
1st Scotch® Mastic Strip 2230 Solder Block
2nd Scotch® Mastic Strip 2230
Trim
Cable
Wire
Shield
Ground Braid Leg
Figure 21
13.5Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 22).
NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.
1-1/2" (38 mm) |
Semi-Con |
Shield Wires |
Constant Force Spring |
Two Half-Lapped Layers of Electrical Grade Vinyl Tape |
Scotch® Mastic Strip 2230 |
Vinyl Tape Marker |
Figure 22
14.0 Install Lug or Connector
Important Packaging Notice
In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination. This shipping core can be recycled with other polypropylene waste.
14.1Check to insure 3M™ Cold Shrink QT -III Silicone Rubber Termination fits over the selected lug or connector. If lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME.
Figure 23