Vulcan-Hart VL2GMS, VL3GMS, VL3GAS, VL2GAS, VL2GSS, VL3GSS, VL3GPS GAS Manifold Pressure Adjustment

Page 33

VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS

2)If a spark from ignitor is present but does not ignite gas before the ignition control module locks out, (90 sec.) there may not be enough gas in the line for ignition. Verify the gas supply and gas combination control valve are both on. Turn the ignition control modules re-set switch OFF then ON to reset the module. Sparking should then resume to ignite gas. The module may need reset several times before ignition takes place.

3)If ignitor is still not sparking proceed to step 3.

3.Check the ignition control module and transformer.

A.Turn the ignition control modules re-set switch OFF then ON to eliminate a lockout condition.

B.Check for 24VAC output on the ignition control module transformer.

1)If 24VAC is present between terminals 5 & 6 on the ignition control module but ignitor is not sparking, then replace ignition control module and re-test.

2)If 24VAC is not present then ensure that transformer is receiving 120VAC input. If ignition control module transformer is receiving proper voltage, then replace ignition control module transformer and re-test.

4.After making the necessary component adjustments or replacements, check for proper operation.

GAS MANIFOLD PRESSURE

ADJUSTMENT

WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED.

WARNING: SHUT OFF THE GAS SUPPLY BEFORE SERVICING THE UNIT.

1.Open the front cabinet doors and turn the gas combination control valve off.

2.To measure the manifold pressure, remove the 1/8 inch NPT plug (pressure tap) on the outlet side of the valve and attach a manometer.

3.Turn the gas combination control valve and the main power switch to ON.

4.After the burner lights, compare the manometer pressure reading to the pressure chart near the end of this procedure.

A.If other appliances are connected to the same gas line, turn them all ON and check manometer pressure reading again. If the pressure drops ½ inch water column or more, then the incoming pressure should be checked. then the gas supply needs to be checked by the gas line installer or the local gas company for adequate sizing.

B.If no other gas appliances are connected to the gas line or the pressure does not drop as described above but the manifold pressure still requires adjustment, proceed to step 5.

5.Remove the adjustment screw cap to access the pressure adjustment screw.

6.After the burner lights, set the pressure as outlined below.

A.To increase pressure, turn the screw clockwise.

B.To decrease pressure, turn the screw counterclockwise.

NOTE: Accurate gas pressure adjustments can only be made with the gas ON and the burner lit.

 

 

 

 

 

 

 

 

 

 

PRESSURE READINGS

 

 

 

 

(INCHES W.C.)

 

 

 

 

 

 

 

 

 

 

GAS TYPE

MANIFOLD

 

LINE

 

 

 

 

 

 

 

 

RECOMMENDED

MIN

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural

4.0

 

7.0

5.0

 

 

 

 

 

 

 

14

 

Propane

10.0

 

11.0

11.0

 

 

 

 

 

 

 

 

 

 

NOTE: If the incoming line pressure is less than the minimum stated, then the manifold pressure can not be set correctly.

Page 33 of 88

Image 33
Contents VL Boiler Base Series Convection Steamers Table of Contents VL Series Steamers Water Conditioning IntroductionTools SpecificationsElectric Steamers Gas SteamersElectrically Powered Steam Boiler Gas Powered Steam BoilerRegenerated Steam Powered Boiler Steamer OperationBoiler Blowdown and Steamer Shut off Direct Steam Powered CookerAutomatic blowdown Manual blowdownStandard Automatic Prevent Cycling Pressure Switch Water Level Gauge AssemblyHigh Limit Pressure Switch Power SwitchDelime Port Assembly Handhole Cover AssemblyBoiler Pressure Gauge Check ValveCooking Timer Compartment Power SwitchThermal Switch Load Compensator Cooking Light RedRemoval and Replacement of Parts VL Series Steamers Removal and Replacement of Parts Cooking Compartment Controls Component Configurations Water Level Controls LOW Level CUT OFF and Differential Water Level Gauge AssemblySolid State Electro MechanicalBoiler Assembly High Limit Thermostat Boiler Fill and Cold Water Condenser Solenoid Valves GAS Combination Control ValveGasket Compartment Gasket and Door Screw NUT, Door and BushingsDoor Screw Nut Door and BushingHeater Contactors Steam CoilHeating Elements Clean-Out All Boiler Models BoilerInspection Deliming Only Models with Deliming Port Assembly Water Level Controls Test Solid State Low level Cut-Off & Differential ControlElectro Mechanical Low level Cut-Off & Differential Control Water Level Probes Compartment Pressure Adjustment DisassemblyFill and Cold Water Solenoid Valves Boiler Blowdown Drain Solenoid Valve Boiler not Filling with WaterNewer Models Boiler Slow to PressurizeOlder Models All Models With BoilerElectric Models Inlet Water StrainerDirect Steam Models Regenerated Steam Coil SteamersVL Series Steamer Service Procedures and Adjustments Air Shutter Adjustment GAS BurnersAutomatic Ignition Systems GAS Models Spark Ignition Control Test TerminalsGAS Manifold Pressure Adjustment Regenerated Steam Older Models Heater Contactors Direct Steam ModelsVL Series Steamer Service Procedures and Adjustments Thermal Switch Prevent Automatic Models Steam Gate Valves Water Level Controls Electrical OperationSolid State Auxiliary Low Level Cut-Off Electro Mechanical Low level Cut-Off & Differential Control Electro Mechanical Auxiliary Low Level Cut-Off Initial Fill and Preheat Sequence of OperationVL Series Steamer Electrical Operation Water Refill After Initial Fill Cook CycleBoiler Blowdown/drain Electric ModelsCook Cycle Water Refill After Initial Fill Purposely Left Blank Manual Ignition, Standard Controls Electronic Ignition, Standard Controls Manual Ignition, CSD-1 Code Controls Electronic Ignition, CSD-1 Code Controls VL Series Steamer Electrical Operation Manual Ignition, Standard Controls VL Series Steamer Electrical Operation Electronic Ignition, Standard Controls VL Series Steamer Electrical Operation Manual Ignition, CSD-1 Code Controls VL Series Steamer Electrical Operation Electronic Ignition, CSD-1 Code Controls VL Series Steamer Electrical Operation Auto Blowdown, Standard Controls Auto Blowdown, Cal-Code Controls Auto Blowdown, Standard Controls contactor 1 std VL Series Steamer Electrical Operation Auto Blowdown, Standard Controls contactors 2 std VL Series Steamer Electrical Operation Manual Blowdown, Cal-Code Controls contactors 1 std aux VL Series Steamer Electrical Operation Auto Blowdown, Cal-Code Controls contactors 1 std aux VL Series Steamer Electrical Operation Auto Blowdown, Cal-Code Controls contactors 2 std aux VL Series Steamer Electrical Operation Manual Blowdown, Cal-Code Controls contactors 2 std aux VL Series Steamer Electrical Operation Standard and Cal-Code/CSD-1 Controls See Schematic and Wiring Diagrams Compartment Controls Manual Blowdown Older Models Auto Blowdown Older Models Schematic and Wiring Diagrams Compartment Controls Automatic Standard Manual ALL Models TroubleshootingContacts not closing to power boiler fill solenoid Schematic and Wiring Diagrams GAS Models only Symptom Possible CausesPilot not adjusted correctly. See Pilot

VL2GPS, VL3GPS, VL3GSS, VL2GSS, VL2GAS specifications

Vulcan-Hart is well-known in the commercial cooking equipment industry, providing durable and efficient products that cater to the needs of restaurants and foodservice operations. Their line of griddles, namely the VL3GAS, VL3GPS, VL3GMS, VL2GAS, and VL2GPS, showcases their commitment to high-quality performance and innovative cooking technologies.

The Vulcan-Hart VL3GAS is a gas griddle, featuring a robust stainless steel construction that ensures longevity and resilience in a bustling kitchen environment. It offers a smooth, hot cooking surface that allows for optimal heat retention and distribution, ensuring that food cooks evenly. With a 3/4-inch thick steel plate, it provides excellent thermal conductivity, making it ideal for high-volume cooking. This model is designed with easy-to-use controls, which makes it convenient for chefs to operate.

The VL3GPS model is a gas-powered griddle that comes equipped with a patented grease management system, which aids in maintaining a cleaner cooking environment. This system helps to separate grease from food and minimizes flare-ups, enhancing safety during cooking. Additionally, the griddle features a temperature control that allows chefs to set precise cooking temperatures, ensuring consistent results.

Moving to the VL3GMS, this model introduces increased versatility with its combination of gas and optional electric features. It’s tailored for establishments that require flexibility in their cooking strategies. The VL3GMS is also designed with a spacious cooking surface, making it suitable for preparing a wide array of dishes simultaneously.

The VL2GAS is a two-burner gas griddle that is specifically tailored for smaller kitchen operations or those with limited space. Its compact design does not compromise on performance, still providing a durable cooking surface and reliable temperature control. This model is ideal for smaller cafes or food trucks where space is at a premium.

Lastly, the VL2GPS complements the VL2GAS with its grease management system. This enhances hygiene and ensures that cooking remains efficient and safe. Both VL2 models offer easy startup and shutdown procedures, making them user-friendly for chefs working in fast-paced environments.

Overall, the Vulcan-Hart VL series griddles combine quality construction, innovative technology, and efficient design. Whether it’s the three-burner or two-burner options, these griddles meet the demands of commercial kitchens, providing reliable cooking solutions that serve the dynamic needs of the foodservice industry.